13
ENGLISH
7.2.3 NV
details
(1) nviRequest
Table 7-2 lists responses to the request modes of nviRequest.
Table 7-2 Responses to nviRequest
Request
Node object response
VSD object response
RQ_NORMAL(0)
- Enables the node object and NVs to
the normal mode.
- Updates nvoStatus and outputs the
new object status.
- Enables the VSD object and NVs to
the normal mode.
- Updates nvoStatus and outputs the
new object status.
RQ_ENABLE(7)
Same as above.
Same as above.
RQ_DISABLE(1)
- Stops the motor if running.
- Keeps the node object enabled.
- Updates nvoStatus and outputs the
new object status.
- Stops the motor if running.
- Disables the VSD object, ignores NV
input, and forbids its output to transmit.
- Updates nvoStatus and outputs the
new object status.
RQ_UPDATE_STATUS(2) - Updates nvoStatus and outputs the
new object status.
- Updates nvoStatus and outputs the
new object status.
RQ_REPORT_MASK(5)
- Reports supported requests as "1."
- Updates nvoStatus and outputs the
new object status.
- Reports supported requests as "1."
RQ_CLEAR_ALARM(10) -
Resets
alarm.
- Updates nvoStatus and outputs the
new object status.
- Resets alarm.
- Updates nvoStatus and outputs the
new object status.
All other requests
- Returns an invalid request
response.
- Updates nvoStatus and outputs the
new object status.
- Returns an invalid request response.
- Updates nvoStatus and outputs the
new object status.
All other objectIDs
- Returns an invalid request
response.
- Updates nvoStatus and outputs the
new object status.
- Returns an invalid request response.
- Updates nvoStatus and outputs the
new object status.
(2) nvoStatus
Table 7-3 lists the status network variables supported and their descriptions.
Table 7-3 Status Network Variables Supported
Status
Description
object_id
Returns the object ID designated by the Request.
invalid_id
Turns "1" when Request is issued to an object with invalid ID.
invalid_request
Turns "1" for an invalid request response.
disabled
Turns "1" when the VSD object is disabled.
in_alarm
Turns "1" when the inverter is in an alarm state or has not solved an alarm.
report_mask
Turns the value of the supported status to "1."
7.2.4 Configuration properties (CPs)
Configuration properties are not supported for the node object.
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...