IMPORTANT!
When configuring "PV Point" backup power mode, the information in chapter
on
page
When configuring "Full Backup" backup power mode, the information in chapter
on page
must be observed.
Backup power nominal voltage
When backup power mode is activated, the nominal voltage of the public grid must be
selected.
State of charge warning limit
A warning is output when the residual capacity of the battery specified here is reached in
backup power mode.
Reserve capacity
The set value results in a residual capacity (depending on the capacity of the battery)
that is reserved for backup power. The battery is not discharged below the residual capa-
city in grid-connected operation.
Load management
Up to four pins can be selected for load management here. Additional load management
settings are available in the "Load management" menu item.
Default: Pin 1
Australia - Demand Response Mode (DRM)
The pins for control via DRM can be set here:
Mode
Description
Information
DRM pin
I/O pin
DRM0
Inverter disconnects
itself from the grid
DRM0 occurs if there is an
interruption or short circuit
on the REF GEN or COM
LOAD leads, or if the com-
binations DRM1 - DRM8
are invalid.
The mains relays open.
REF GEN
COM
LOAD
IO4
IO5
DRM1
Import P
nom
≤ 0%
without disconnection
from the grid
currently not supported
DRM 1/5
IN6
DRM2
Import P
nom
≤ 50%
currently not supported
DRM 2/6
IN7
DRM3
Import P
nom
≤ 75% &
+Q
rel
* ≥ 0%
currently not supported
DRM 3/7
IN8
DRM4
Import P
nom
≤ 100%
currently not supported
DRM 4/8
IN9
DRM5
Export P
nom
≤ 0%
without disconnection
from the grid
currently not supported
DRM 1/5
IN6
DRM6
Export P
nom
≤ 50%
currently not supported
DRM 2/6
IN7
DRM7
Export P
nom
≤ 75% &
-Q
rel
* ≥ 0%
currently not supported
DRM 3/7
IN8
DRM8
Export P
nom
≤ 100%
currently not supported
DRM 4/8
IN9
The percentages always refer to the nominal device output.
IMPORTANT!
If the Demand Response Mode (DRM) function is enabled and no DRM control is con-
nected, the inverter switches to Standby mode.
95
EN
Содержание Primo GEN24 3.0 Plus
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Backup power variant Full Backup 35...
Страница 36: ...36...
Страница 43: ...Installation 43...
Страница 44: ...44...
Страница 50: ...Do not install the inverter on the ceiling 50...
Страница 84: ...84...
Страница 90: ...90...
Страница 91: ...Settings website of the inverter 91...
Страница 92: ...92...
Страница 110: ...I O power man agement settings 4 relays 110...
Страница 112: ...I O power man agement settings 3 relays 112...
Страница 114: ...I O power man agement settings 2 relays 114...
Страница 118: ...118...
Страница 119: ...Options 119...
Страница 120: ...120...
Страница 129: ...Appendix 129...
Страница 130: ...130...
Страница 143: ...Circuit diagrams 143...
Страница 144: ...144...
Страница 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Страница 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Страница 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Страница 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Страница 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Страница 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Страница 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Страница 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Страница 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Страница 155: ...Dimensions of the inverter 155...
Страница 156: ...156...
Страница 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Страница 158: ...158...
Страница 159: ...159 EN...