Connecting the
battery commu-
nication cables
1
Strip 10 mm from the single conductors
and mount the ferrules if necessary.
IMPORTANT!
Connect the individual conductors to an
appropriate ferrule if several individual
conductors are connected to one input of
the push-in terminals.
2
Insert the cable into the respective slot
and check the cable is securely retained.
IMPORTANT!
Use only twisted pairs for connecting
"Data +/-" and "/-", see section
Permitted cables for the data commu-
nication area
.
Twist the cable shield and insert into the
"SHIELD" slot.
IMPORTANT!
Improperly fitted shielding can cause data
communication problems.
For the wiring proposal recommended by Fronius, see page
.
Terminating res-
istors
It may be possible for the system to function without terminating resistors. However,
owing to interference, the use of terminating resistors according to the following overview
is recommended for trouble-free functioning.
For permissible cables and max. distances see chapter
on page
.
IMPORTANT!
Terminating resistors that are not positioned as illustrated can result in interference in the
data communication. If the terminating resistor on the battery cannot be deactivated, the
battery is to be set up at the bus end (see option 2, 3).
83
EN
Содержание Primo GEN24 3.0 Plus
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Backup power variant Full Backup 35...
Страница 36: ...36...
Страница 43: ...Installation 43...
Страница 44: ...44...
Страница 50: ...Do not install the inverter on the ceiling 50...
Страница 84: ...84...
Страница 90: ...90...
Страница 91: ...Settings website of the inverter 91...
Страница 92: ...92...
Страница 110: ...I O power man agement settings 4 relays 110...
Страница 112: ...I O power man agement settings 3 relays 112...
Страница 114: ...I O power man agement settings 2 relays 114...
Страница 118: ...118...
Страница 119: ...Options 119...
Страница 120: ...120...
Страница 129: ...Appendix 129...
Страница 130: ...130...
Страница 143: ...Circuit diagrams 143...
Страница 144: ...144...
Страница 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Страница 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Страница 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Страница 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Страница 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Страница 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Страница 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Страница 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Страница 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Страница 155: ...Dimensions of the inverter 155...
Страница 156: ...156...
Страница 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Страница 158: ...158...
Страница 159: ...159 EN...