
Permitted cables
for the data com-
munication area
Cables with the following design can be connected to the terminals of the inverter:
-
Copper: round, solid
-
Copper: round, fine-stranded
IMPORTANT!
Connect the individual conductors to an appropriate ferrule if several individual conduct-
ors are connected to one input of the push-in terminals.
WSD connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
100 m
109 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
min. CAT 5
UTP (unshiel-
ded twisted
pair)
Modbus connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
300 m
328 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
min. CAT 5
STP (shielded
twisted pair)
IO connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
30 m
32 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
Single con-
ductor pos-
sible
LAN connections
Fronius recommends using at least CAT 5 STP (shielded twisted pair) cables and a maximum distance of
100 m (109 yd).
Cross section of
the AC cable
For a standard M32 metric screw joint with a reducer:
Cable diameter from 7-15 mm
When using an M32 metric screw joint (reducer removed):
cable diameter from 11-21 mm
(with a cable diameter of less than 11 mm, the strain-relief force is reduced from 100 N to
a maximum of 80 N)
55
EN
Содержание Primo GEN24 3.0 Plus
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Backup power variant Full Backup 35...
Страница 36: ...36...
Страница 43: ...Installation 43...
Страница 44: ...44...
Страница 50: ...Do not install the inverter on the ceiling 50...
Страница 84: ...84...
Страница 90: ...90...
Страница 91: ...Settings website of the inverter 91...
Страница 92: ...92...
Страница 110: ...I O power man agement settings 4 relays 110...
Страница 112: ...I O power man agement settings 3 relays 112...
Страница 114: ...I O power man agement settings 2 relays 114...
Страница 118: ...118...
Страница 119: ...Options 119...
Страница 120: ...120...
Страница 129: ...Appendix 129...
Страница 130: ...130...
Страница 143: ...Circuit diagrams 143...
Страница 144: ...144...
Страница 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Страница 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Страница 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Страница 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Страница 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Страница 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Страница 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Страница 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Страница 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Страница 155: ...Dimensions of the inverter 155...
Страница 156: ...156...
Страница 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Страница 158: ...158...
Страница 159: ...159 EN...