Backup power
This system has backup power functions. This enables a replacement power supply to
be established in the event of a failure in the public grid.
Where an automatic backup power supply is installed, a
(https://www.fronius.com/en/search-page, item number: 42,0409,0275) must be fitted on
the electrical distributor.
Maintenance and installation work in the home network requires both disconnection on
the utility side and deactivation of the replacement power mode by opening the integ-
rated DC disconnector on the inverter.
Depending on the insolation conditions and the battery state of charge, the backup
power supply is automatically deactivated and activated. This can cause the backup
power supply to unexpectedly return from standby mode. Therefore, installation work can
only be performed on the home network when the backup power supply is deactivated.
Influencing factors on the total power in backup power mode:
Reactive power
Electrical loads with a power factor not equal to 1 also require reactive power in addition
to effective power. The reactive power also loads the inverter. Therefore, to correctly cal-
culate the actual total power, it is not the rated power of the load that is relevant, but the
current caused by effective and reactive power.
Devices with a high reactive power are mainly electric motors such as:
-
Water pumps
-
Circular saws
-
Blowers and fans
High starting current
Electrical loads that need to accelerate a large mass usually require a high starting cur-
rent. This can be up to 10 times higher than the nominal current. The maximum current
of the inverter is available for the starting current. Loads with too high starting currents
therefore cannot be started/operated, even though the nominal power of the inverter sug-
gests that they can. When dimensioning the backup power circuit, the connected load
power and any starting current must also be taken into account.
Devices with high starting currents are, for example:
-
Devices with electric motors (e.g. lifting platform, circular saws, planing bench)
-
Devices with large transmission ratio and flywheel mass
-
Devices with compressors (e.g. compressed air compressors, air conditioning sys-
tems)
IMPORTANT!
Very high starting currents can cause short-term distortion or a drop in output voltage.
The simultaneous operation of electronic devices in the same backup power supply sys-
tem should be avoided.
IMPORTANT!
The inverter may only be operated within the limits of its technical capabilities. Operation
outside of its technical capabilities can cause the inverter to shut down.
Data protection
The user is responsible for the safekeeping of any changes made to the factory settings.
The manufacturer accepts no liability for any deleted personal settings.
Copyright
Copyright of these operating instructions remains with the manufacturer.
9
EN
Содержание Primo GEN24 3.0 Plus
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Backup power variant Full Backup 35...
Страница 36: ...36...
Страница 43: ...Installation 43...
Страница 44: ...44...
Страница 50: ...Do not install the inverter on the ceiling 50...
Страница 84: ...84...
Страница 90: ...90...
Страница 91: ...Settings website of the inverter 91...
Страница 92: ...92...
Страница 110: ...I O power man agement settings 4 relays 110...
Страница 112: ...I O power man agement settings 3 relays 112...
Страница 114: ...I O power man agement settings 2 relays 114...
Страница 118: ...118...
Страница 119: ...Options 119...
Страница 120: ...120...
Страница 129: ...Appendix 129...
Страница 130: ...130...
Страница 143: ...Circuit diagrams 143...
Страница 144: ...144...
Страница 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Страница 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Страница 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Страница 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Страница 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Страница 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Страница 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Страница 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Страница 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Страница 155: ...Dimensions of the inverter 155...
Страница 156: ...156...
Страница 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Страница 158: ...158...
Страница 159: ...159 EN...