Settings related to Modbus communication. Set your
Modbus
Address and the preferred
baud
rate,
the
number
of
stop
bits
and
Parity
.
•
Modbus
Activation
- activation/deactivation of the Modbus protocol.
•
Editing
of
Parameters
- permission to edit parameters with the Modbus protocol.
•
Recuperator
control
- permission to control the recuperator with the Modbus protocol.
•
Modification
lock
- activation/deactivation of locking parameter modification. When this function is activated, only
some of the controller parameters (such as ON/OFF or Modbus settings) can be changed, while other parameters
will be locked for editing.
Cleaning
the
heat
exchanger
•
Activation
interval
-
days
- setting the number of days, after which cleaning of the exchanger should start.
•
Start
time
of
cleaning
- start time of the cleaning procedure. It is the time at which cleaning is started on the
scheduled cleaning day.
Inspection
settings
Settings related to switching the general inspection and the recuperator interlock support on or off.
•
Maintenance
function
support
- enable or disable the notification about the necessity to perform periodic
inspection.
•
Resetting
work
day
counter
- resetting the number of working days of the device, in order to calculate the time left
to inspection and to lock operation of the unit.
•
Number
of
days
to
inspection
- setting the number of days to notify about the necessity to perform periodic
inspection - it is determined by the installer, in accordance with the manufacturer's recommendations.
Additional
service
settings
•
Calibrate
touch
panel
-
Adjusts the touch response precision for the control panel.
•
Default
Settings
- if the
Restore
default
settings
for
panel/ecoVENT
parameter is set to
YES
, all changes are cancelled
and default (factory) settings restored.
8.19
Technical
Data
Power supply/current consumption
(controller only)
230V~, 50Hz/40mA
Max. rated current
6 (6)A
Ambient/storage temperature
0...+40
°
C/-25..+50
°
C
Relative humidity
5 - 85%, without vapour condensation
Temperature measuring range of the NTC
10K sensor
-20
…
+125
°
C
Network screw-in splice connectors
Cross-section 0.5...2.5mm
2
, tightening torque 0.55Nm, 7mm isolation
Signal screw-in splice connectors
Cross-section 0.25...1.5mm
2
, tightening torque 0.235Nm, 7mm
isolation
Display
Colour Graphic, 480x272 with a touch panel
Standard
PN-EN 60730-2-9, PN-EN 60730-1
Software class
A (acc. to PN-EN 60730-1)
Protection rating
To be built into Class I instruments
Level of contamination
Level 2 (acc. to PN-EN 60730-1)
Inputs/outputs
Analogue inputs
AI0-AI6
Digital inputs
DI0-DI4
Analogue outputs
AO0-AO5, whereas:
- 2 outputs (0-10V)
- 2 outputs (PWM)
- 2 PWM outputs or (0-10V), programmable switching outputs
Communication outputs
3xRS485, of which one is separated
Outputs with a potential-free contact
- 3 (NO) normally open,
- 2 (NO/NC), switchable
Power outputs
- 2 (NO), 1000W
- 2 (NO), 750W
Potential signalling outputs
- 3 (NO), 230V~
8.20
Operating
conditions
Controller: