Operation and Maintenance Manual
OnyX Pride Recuperators February 2019
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice.
Page
27
CAUTION!
In
the
regions
characterised
by
high
dust
levels
in
the
air,
it
is
recommended
to
check
the
condition
of
the
filter
cloth
more
frequently.
CAUTION!
When
inspecting,
make
sure
that
none
of
the
filter
elements
has
been
torn
(e.g.
from
excessive
soiling).
CAUTION!
Regular
changing
of
filters
is
essential
to
maintain
the
correct
performance
parameters
and
energy
efficiency
of
your
system
.
CAUTION!
Recuperators
with
the
nominal
capacity
of
<1000m3/h
are
equipped
with
a
filter
change
warning
system
controlled
by
a
timer.
In
recuperators
with
the
nominal
capacity
of
>1000m3/h,
a
warning
signal
is
activated,
when
the
final
value
of
pressure
drop
in
the
filter
is
exceeded.
7.2
Heat
recovery
system.
The condition of the heat exchanger should be checked once every six months. If necessary, clean the heat exchanger with
compressed air or a vacuum cleaner. In addition, check the following: the level of soiling in the condensate tank; whether
the water trap is unobstructed and filled with water; and whether that the bypass damper rotates freely.
7.3
Electric
heater.
The level of soiling in the heater should be checked on a quarterly basis. This operation may only be carried out, when power
supply to the unit has been disconnected. If necessary, clean the heater with compressed air (directing its flow in the
opposite direction to the normal direction of air flow and parallel to the lamellas), or using a vacuum cleaner with a soft