Operation and Maintenance Manual
OnyX Pride Recuperators February 2019
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice.
Page
16
•
Electrically connect the controller and the panel.
The controller module must be installed in such a way that:
•
a degree of protection appropriate to the environmental conditions in which the module will be used is ensured.
CAUTION!
Keep
a
safe
distance
of
≥
1cm
between
terminals
of
the
module
and
the
conductive
components
of
the
enclosure
•
Protect connection cables against tearing out, loosening, or stressing.
Sample installation, when the module is built in.
5.6.4
Electrical
connection
The controller is powered with 230V~/50Hz voltage - it is connected to the following terminals: L. N, and PE.
The installation should:
•
use a three-wire cable with a protective conductor,
•
and be carried out in accordance with applicable laws.
CAUTION!
If
the
controller
is
switched
off
using
the
keyboard,
dangerous
voltage
may
occur
at
the
terminals
of
the
controller.
Before
starting
any
installation
work,
it
is
essential
to
disconnect
power
supply
and
make
sure
that
no
dangerous
voltage
is
present
on
the
cables.
CAUTION!
Connecting
the
mains
voltage
to
the
digital
input
terminals
and
to
the
analogue
and
transmission
outputs
will
damage
the
controller
and
pose
a
risk
of
electric
shock.
CAUTION!
Connect
the
protective
conductor
of
the
power
supply
cable
to
the
PE
input
of
the
module,
the
terminal
on
the
housing,
and
to
the
protective
conductors
of
the
connected
devices.
CAUTION!
All
peripheral
devices
must
be
connected
by
the
installer,
in
accordance
with
the
applicable
regulations.
Follow
the
safety
precautions
for
electric
shock.
The ecoVENT panel
8 x M3 nut
3 x PST-8-01 pin
4 x washer
Ø
3
4 x M3x25 bolt hexagonal head