Frapol OnyX Pride 400 Скачать руководство пользователя страница 22

Operation and Maintenance Manual

 OnyX Pride Recuperators February 2019 

 

 

Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. 

Page

 22

 

 

 

 

 

Plug the power plug into the mini USB port socket, and connect the 3G USB port to the ecoLINK2 interface. Use the Ethernet 
cable to connect the RJ45 Ethernet port, for example, to an ADSL router, a switch, or a modem. You do not need to use this 
socket , if there is access to wireless Wi-Fi. 
After connecting power supply, the ecoNET300 Internet module will take approximately one minute to load the operating 
system. Only after the system has been loaded, the module starts operating and signals its status with LED controls. 

 

After the module has successfully connected to the controller, additional options will appear in the main menu of the 
controller: 

 

Menu

 → 

Information

 → 

ecoNET

 

WiFi

 

 

Menu

 → 

Information

 → 

ecoNET

 

Ethernet

 

 

Menu

 → 

General

 

settings

 → 

WiFi

 

When connecting both to LAN and WiFi networks, EcoNET300 requires that the Access Point (network access point), e.g. a 
router, has a DHCP server switched on, as manual IP address assignment is not supported for the module. Connecting to a 
WiFi network requires the following settings: network name (SSID), type of protection, access password

.

 

 

Connecting to a wired LAN network 

Menu

 → 

Information

 → 

ecoNET

 

Ethernet

 

Here, you can find the IP number, mask, Gateway, check the connection status to the econet24 server. It is required to save 
the displayed IP number (sample IP: 10.1.2.237). This number, in the form of: http://10.1.2.237, must be entered in the 
address  bar  of  your  web  browser,  from  the  LAN  network  level.  When  entered,  it  will  open  a  web  page  to  operate  the 
controller menu. 
In the case of a wireless connection (Wi-Fi), it is necessary to enter the parameters of this network in the menu of the 
controller. 

Menu

 → 

General

 

settings

 → 

Wi-Fi

 

 

SSID

 - enter the name of a local wireless network 

 

Protection

 

type

 - select and confirm the type of encryption for a given Wi-Fi network (the most common type of 

encryption is WPA2) 

 

Password

 

- enter the password to access the Wi-Fi network

 

Use 

Menu

 → 

Information

 → 

ecoNET

 

WiFi

 

to read the IP number, mask, gateway, and the connection status to the ecoNET 

server. 
Logging into your ecoNET account 

ON/RESET button Deleting user 

name 

and 

password 

and 

restoring  to  default  settings, 

user: admin, 

password: admin. Works only in 

the local version 

LEDs  indicating  the  operating 

status of the module. 

Connection 

to the server 

No light

There is no connection to the 
ecoNET24.com external server 

Connection to the external 
ecoNET24.com server has been 
established. 

Lights up 

No light 

Connection 

to Wi-Fi 

Lights up 

No light 

Connection to a programmed 
wireless network has been 
established. 

There is no connection to a 
wireless network. 

There is no connection 
to the boiler controller. 

LED 

Power supply 

Lights up

Power on 

Power supply switched off 

No light 

Connection 
to the 
controller 

Lights up

Connection to the boiler controller 
has been established. 

LED status 

Operational status of ecoNET300 

Содержание OnyX Pride 400

Страница 1: ...ation and Maintenance Manual OnyX Pride Recuperators February 2019 Frapol Sp z o o reserves the right to introduce changes without any prior notice Page 1 OPERATION AND MAINTENANCE MANUAL for Recupera...

Страница 2: ...100 3 8 Product data sheets and energy related labels 111 4 Transport and storage 122 5 Installation 12 5 1 Place of assembly 122 5 2 Assembly sequence 122 5 3 Connecting ventilation ducts 132 5 4 Ai...

Страница 3: ...eneral Settings 343 8 14 Working with the Internet module 355 8 15 Alarms 39 8 16 Assembly instructions and operational settings for the SMART controller 410 8 17 Installer Menu 421 8 18 Description o...

Страница 4: ...rameters of the power supply line and its necessary protective equipment must be selected and dimensioned by personnel with appropriate qualifications regarding designing electrical installations in a...

Страница 5: ...be carried out by an authorized service centre and using original spare parts MODIFICATIONS Unauthorized modifications to the device mechanical or electrical are not permitted and void the warranty T...

Страница 6: ...e 2 1 Residual hazards In the process of designing and manufacturing of the devices solutions were applied that minimise the possibility of hazards to persons and property However this does not elimin...

Страница 7: ...s the most important technical parameters of the device A sample rating plate This Maintenance and Operational Manual is provided to the customer together with an invoice warranty and declaration of c...

Страница 8: ...em 2 Fresh air 3 and recovery room air 4 filters Supply 5 and extract air 6 fans An automation system 7 with a main switch and a power supply socket Adjustable attachment fittings for inspection flaps...

Страница 9: ...changes without any prior notice Page 9 3 4 External dimensions 3 4 1 OnyX Pride 400 3 5 Capacity range 3 5 1 OnyX Pride 400 0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 spr dyspozycyjny Pa...

Страница 10: ...power consumption is determined for the external static pressure of 100 Pa CAUTION The manufacturer is not responsible for reduced efficiency of heat recovery resulting from improper operation and im...

Страница 11: ...29m3 h 50Pa all components of the recuperator clean and dry 3 8 Product data sheets and energy related labels 3 8 1 OnyX Pride 400 Product data sheet technical data in accordance with Regulation of th...

Страница 12: ...is a high level of dustiness gypsum finish residues or residues after scraping floors Before installing the appliance a visual inspection of the general condition of the appliance must be carried out...

Страница 13: ...e ventilation ducts using shut off dampers or automatic shut off flaps Otherwise there is a risk of damage to the unit resulting from flooding the unit with condensate accumulated in the ventilation d...

Страница 14: ...used in an environment in which condensation of vapour takes place and must not be exposed to water Provide protection against the ingress of dust and water The controller is designed as a module to b...

Страница 15: ...on is ensured over distances of up to 100m from the device without any additional surge protections and signal amplification The cable may be recessed in the wall or run along its surface Do not run a...

Страница 16: ...hree wire cable with a protective conductor and be carried out in accordance with applicable laws CAUTION If the controller is switched off using the keyboard dangerous voltage may occur at the termin...

Страница 17: ...ed with screw in splice connectors adapted for accepting cables with a sleeve tip plugged in sockets Cable ends especially those transferring mains voltage must be protected against delamination for e...

Страница 18: ...ation and Maintenance Manual OnyX Pride Recuperators February 2019 Frapol Sp z o o reserves the right to introduce changes without any prior notice Page 18 5 6 5 Electrical diagram of the controller b...

Страница 19: ...ly air duct SBP2 heat exchanger bypass actuator exhaust air duct OPERATION potential free contact NO FAILURE potential free contact NO RESERVE 1 2 potential free contact NO Analogue outputs N2 pre hea...

Страница 20: ...sources incorrect temperature indication The minimum distance between such cables 40cm The sensors must be connected to the controller according to the wiring diagram To check the sensors measure the...

Страница 21: ...e must be connected to the controller module via the ecoLINK2 interface and the EL2 adapter Connect the pick up socket 1 with the ecoLINK2 interface connect the terminals 3 to the Frapol Smart display...

Страница 22: ...ver It is required to save the displayed IP number sample IP 10 1 2 237 This number in the form of http 10 1 2 237 must be entered in the address bar of your web browser from the LAN network level Whe...

Страница 23: ...er the UID number of the controller Controller label enter any name for your controller Advanced user Edition of service parameters select this box in order to be able to change service parameters of...

Страница 24: ...l load present in these circuits is lower The table below shows the approximate rating values for a fuse depending on the load Load W Fuse rating A 300 1 00 380 1 25 480 1 60 580 2 00 730 2 50 920 3 1...

Страница 25: ...f the electric heater to the mains must be confirmed by a report drawn up after measuring the insulation of the supply cable and the electric shock protection After switching off the heater the automa...

Страница 26: ...llowing Recuperator Control panel Supply and extract air diffusers located in the rooms Fresh air intake and exhaust air discharge grilles Ventilation ducts included in the recuperation system CAUTION...

Страница 27: ...is activated when the final value of pressure drop in the filter is exceeded 7 2 Heat recovery system The condition of the heat exchanger should be checked once every six months If necessary clean th...

Страница 28: ...nsor 8 2 Main screen Key 1 Adjustment mode OPERATION OPERATION heating OPERATION cooling Cleaning the heat exchanger Thawing Standstill 12 Temperature of extracted air C 2 Exhaust fan air flow 13 Pre...

Страница 29: ...eater External temperature weather Ground floor Downtime schedule Ventilating Shutdown schedule Exit Overpressure User modes I II III IV 8 3 Operation The device features a touch screen display Select...

Страница 30: ...speed difference Duration of exit mode User mode 1 2 3 4 User mode 1 2 3 4 Pre set temperature Supply air fan speed Exhaust air fan speed Continuous mode settings Supply air fan speed Exhaust air fan...

Страница 31: ...ger Thawing the controller carries out the process of defrosting the exchanger it is a master algorithm and the user has no influence on the operation parameters of the air handling unit STANDSTILL th...

Страница 32: ...l is ignored when the value of reduction is set to 0 even if a number of hours has been defined 8 8 Working modes To set the main operating mode and additional operating modes for the controller accor...

Страница 33: ...n speed and Extract air fan speed in the control mode with constant air flow in the fans 8 9 Schedules Enabling or disabling the recuperator depending on schedule settings The available Work schedule...

Страница 34: ...he air intake damper and opens the GHE damper for the intake of air to the recuperator through the GHE when the outside temperature is above the Winter opening temperature e g in autumn and winter per...

Страница 35: ...pool Parental control if this function is active the menu cannot be accessed Touch the screen for approx 3 seconds to unlock you will see an animation showing the opening of a padlock Name of ecoSTER...

Страница 36: ...e managing of the controller operation via a Wi Fi LAN network and the website owned by www econet24 com The user can use a PC a tablet or a phone with a web browser to remotely monitor the operation...

Страница 37: ...Operation and Maintenance Manual OnyX Pride Recuperators February 2019 Frapol Sp z o o reserves the right to introduce changes without any prior notice Page 37...

Страница 38: ...X Pride Recuperators February 2019 Frapol Sp z o o reserves the right to introduce changes without any prior notice Page 38 Interface of the ecoNET apk app with sample settings The mobile ecoNET apk a...

Страница 39: ...ecorded then the alarm disappears Exhaust air temperature sensor is defective The sensor has been damaged has been connected incorrectly or not configured Signalling of alarm stopping the recuperator...

Страница 40: ...m procedure Continuously from the moment the cause is recorded Possible overheating of the pre heater A thermostat that prevents the unit from overheating has been triggered which may require a reset...

Страница 41: ...a thermostat NO NC 18 Exhaust temperature sensor from the room NTC type 19 Exhaust 20 Supply air temperature sensor NTC type 21 Supply air 22 ecoSTER TOUCH room panel with a room thermostat function...

Страница 42: ...pre heater Electric re heater Ground Heat Exchanger Operation Failure Cooler Manual control setting 0 100 Re heater control SBP1 control SM1 control Radiator control Air supply fan control Exhaust air...

Страница 43: ...200 Number of stop bits 1 stop bit 2 stop bits Parity None Even Odd Modbus activation No Yes Parameter edition No Yes Recuperator control No Yes Modification lock No Yes Default settings Panel default...

Страница 44: ...cording to the wiring diagram Heater thermostats settings related to the thermostats in the pre and re heaters Determine the rest state for the thermostat contact corresponding to the heater in use an...

Страница 45: ...ration of the unit Number of days to inspection setting the number of days to notify about the necessity to perform periodic inspection it is determined by the installer in accordance with the manufac...

Страница 46: ...anty This warranty is valid in the Republic of Poland FRAPOL Sp z o o provides warranty and post warranty service of the device The warranty covers free of charge repairs within 24 twenty four months...

Страница 47: ...eet is available as a pdf document in an editable format xls sheet The costs related to processing a warranty claim during the warranty term shall be borne by Frapol Sp z o o If any discrepancies are...

Страница 48: ...f the Warranty Card Equipment Handover Report Customer Name and address of the facility Type and size of the unit Factory No of the unit Delivery date Assembly and Commissioning Activity Name and addr...

Страница 49: ...signed m3 h Measured m3 h Difference Designed m3 h Measured m3 h Difference CAUTION Returning a filled in equipment handover report within 30 days from the date of commissioning constitutes the basis...

Страница 50: ...February 2019 Frapol Sp z o o reserves the right to introduce changes without any prior notice Page 50 FRAPOL Sp z o o ul Mierzeja Wi lana 8 30 832 Krak w Tel 48 12 653 27 66 48 12 659 05 77 Fax 48 1...

Отзывы: