8.17
Installer
Menu
CAUTION!
This
menu
is
available
only
after
entering
the
installer's
password.
In order to activate additional system components (reheater/after cooler, ground heat exchanger damper, kitchen hood
input R1/R2, air quality sensor input), it is necessary to:
•
Switch off the recuperator in the radial menu using the
"
switch off recuperator
"
button
•
Access the service menu
•
Enter the password for accessing the installer menu
•
Configure the controller on the tabs
•
Output configuration (heaters/coolers/GHE damper)
•
Inputs configuration (measuring elements, inputs R1/R2)
Maximum air flow
[0-10,000]
Filter settings
Reset filter operation counter
[Yes/No]
Manual control
[ON/OFF]
Supply air fan, Exhaust air fan, Electric pre-heater, Electric re-heater, Ground Heat Exchanger, Operation, Failure,
Cooler
Manual control setting
[0-100%]
Re-heater control
SBP1 control
SM1 control
Radiator control
Air supply fan control
Exhaust air fan control
Information
Hardware configuration of recuperator outputs
GHE support
[Yes/No]
Re-heater type
[None / Digital electric /
Analogue electric / Digital water
/ Analogue water]
Pre-heater support
[Off / Electric / Water]
SM1 damper control
[Yes/No]
Radiator support
[Yes/No]
Bypass damper 2 support
[No/Yes]
SM1 settings:
[SM1 minimum control /
SM1 maximum control]
Configuration of potential-free contacts
Actuator power supply
[None / Heat recovery / Radiator
/ Heater]
Reserve 1
[None / Heat recovery / Radiator
/ Heater]
Reserve 2
[None / Heat recovery / Radiator
/ Heater]
Cooling demand threshold
Heating demand threshold
Hardware configuration of recuperator inputs
Air quality sensor
[No/Yes]
Air quality sensor support
No / Analogue CO2 sensor /
Analogue humidity sensor /
Digital sensor]
Heater thermostats
Pre-heater thermostat
[Normally Open/Normally
Closed]
Re-heater thermostat
[Normally Open/Normally
Closed]