Operation and Maintenance Manual
OnyX Pride Recuperators February 2019
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice.
Page
43
R1/R2 input settings
R1/R2 input working mode
[None / Hood / Filter pressure
switches]
R1 input logical status
[Normally Open/Normally
Closed]
R2 input logical status
[Normally Open/Normally
Closed]
Hood mode settings
Supply air fan, controlled with R1
[-100-100%]
Exhaust air fan, controlled with R1
[-100-100%]
Supply air fan, controlled with R2
[-100-100%]
Exhaust air fan, controlled with R2
[-100-100%]
Fan settings
Air supply fan minimum control
[25-100%]
Air supply fan maximum control
[75-100%]
Exhaust air fan minimum control
[25-100%]
Exhaust air fan maximum control
[75-100%]
Air supply fan stop delay
[0..20min]
Minimum outside temperature
Permitted from min. outside temp.
[No/Yes]
Min. outside temperature
[-20..20
º
C]
Hysteresis of min. outside temp.
[0..10
º
C]
Inspection settings
Inspection function support
[On/Off]
Resetting work day counter
[No/Yes]
Number of days to inspection
[30..160]
Modbus settings
Modbus address
[0..200]
Baud rate
[9600/19200/115200]
Number of stop bits
[1 stop bit /2 stop bits]
Parity
[None/Even/Odd]
Modbus activation
[No/Yes]
Parameter edition
[No/Yes]
Recuperator control
[No/Yes]
Modification lock
[No/Yes]
Default settings
Panel default settings
ecoVENT default settings
Touch panel calibration
8.18
Description
of
Installer
Menu
Maximum
energy
expenditure
in
the
recuperator
Setting the maximum energy expenditure for the recuperator in use.
Filter
settings
Settings related to anti-soiling filters.
•
Resetting
filter
operation
counter
- this setting is used to erase the counter displaying the number of days the filter
has been in operation, which will clear the alarms requiring changing the filter, and the counting of filter working
days will start anew.
Manual
control
The menu enables manual control of individual automation elements, by switching them on and off.
Manual
control
settings
Setting the speed of analogue outputs in manual control.
Information
It contains various information about the operation of the controller: values of the measured temperatures, statuses of
outputs and inputs, software versions, etc.
Hardware
configuration
of
recuperator
outputs
The controller can be programmed to control individual recuperator outputs, which affects the control of devices connected
to these outputs.