Flexball Italiana S.r.l.
85
16. Programming of actuators with electronic engine and
electronic gearbox
16.1. Electrical wiring
For electrical wiring please refer to chapter 10.
16.2. Specific parameters
Installations with electronic gearbox might require a delay time when you pass the lever directly from reverse
to forward or from forward to reverse. Factory setting is 0,5 seconds.
Parameter list
Display
code
Description
Values
Factory value
Value shown on
display (factory
value)
Note
dI
Delay in switching off
the gearbox
0 .. 9,9 s
0,0 s
00
dA
Delay in start of throttle
0 .. 9,9 s
0,0 s
00
dF
Delay in neutral; it
occurs any time you
move
directly
from
forward to reverse or
from reverse to forward.
This delay does not
occur
when
from
neutral you move to
forward or reverse.
0 .. 9,9 s
0,5 s
05
L1
These parameters are present only in system with electronic engine with ECU
and/or electric engine inverter driven. Parameters for the voltage outputs are
described at section 14.3.2.
H1
C1
L2
H2
C2
L3
H3
C3
L4
H4
C4
CC
To be used for the check-up of the internal CANBus communication