General operation
Seite/Page 210 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation
22.3.11
11.8.6 Configuration and adjustment
11.8.6.1 Configuration and setting sheet KE05
Standard Jumperung for use as Slave-Panel in connection with two Master-Slave-Adapters RE0706 and a Genera-
tor Control Panel P6+ RE0703 as Master-Panel. Panel only for 12V-Betrieb.
The safety device is installed with the value 0,63AT. The circuit parts for 24V-operation are not equipped.
Fig. 11.8.6-1: Settings of soldered jumper for this configuration (column Conf.)
The solder jumpers are marked on the printed circuit board (with jumper no. and at three-part solder jumper with soldering surface no.)
X
= Jumper must be so set
XM
= Jumper, function must be so set on the master panel is selected
M
= Jumper must be set exactly the same, as on the master panel,
(1): Equivalent resistance for load control lamp e.g. for use with three-phase alternator also integrated automatic controller of Bosch. The resistance value is 68
Ω
3W,
i.e. only for 12V.
(2): A closed contact switches the appropriate input to GND.
Jumper
Status
Conf.
Description
J1
closed
during operation of the start button heat is along-operated
open
XM
Function deactivated
J3
1-2
Dynamo excitation resistor 68R is switched on with Fuel-Pump (1)
2-3
Dynamo excitation resistor 68R is switched on with Panel-ON (1)
open
XM
Dynamo excitation resistor is deactivated
J101
closed
M
12V - operation
open
M
24V - operation (not possible)
J201
1-2
T-Engine-input, for contact, which opens in case of error (2)
2-3
XM
T-Engine-input, for contact, which closes in case of error (2)
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
XM
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203
1-2
Oil-Press-input, for contact, which opens in case of error (2)
2-3
XM
Oil-Press-input, for contact, which closes in case of error (2)
J204
1-2
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
XM
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
T-Winding-input, for contact, which opens in case of error (2)
2-3
XM
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
M
Input Water leak has red LED and switches off
2-3
M
Input Water leak has yellow LED and does not switch off
J207
1-2
M
Input AC-Fault has red LED and switches off
2-3
M
Input AC-Fault has yellow LED and does not switch off
J208
1-2
M
DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3
M
DC-Control-Signal (+) = OK three-phase DC-alternator
J209
1-2
M
DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3
M
DC-Control-Signal (+) = OK three-phase DC-alternator
J210
closed
Input AC-Fault has Pull-Up-current
≥
10mA
open
XM
Input AC-Fault has Pull-Up-current
≥
2,5mA