Generator Faults
Seite/Page 146 Panda PMS 8.000 NE - 42 NE Manual.R05 - Kapitel/Chapter 7: Generator Faults
22.3.11
7.4.15.1 Details and explanations concerning the troubleshooting flowchart
Each failure position in the flowchart above contains a reference number.
With this reference number, the corresponding work steps can be taken from the list below.
1.1 Fuse at the remote control panel.
Execute the fuse exchange as indicated in the data sheet of your remote control panel. Please note that not all
remote control panels do have a corresponding fuse.
1.2 Correct the wiring.
Get the wiring of the generator and the wiring of the external components checked according to the installation
instructions in this manual and the data sheets, as well as desciptions of the external components and correct them
if necessary.
Attention: Voltage up to 400V - Danger to life!
These operations are to be executed by a trained professional
only!
2.1 Exchange DC fuse (Fuse for the starter circuit) - see wiring scheme
Exchange the relevant fuses at the generators’ terminal block.
A defective fuse is not always visually detectable. Measure the fuse with a multimeter for connecting passage.
2.2 Exchange anti-repeat starter device.
Loosen the connecting plug of the anti-repeat starter device.
Loosen the holding screws of the anti-repeat starter device.
Mount the new anti-repeat starter device in reversed order.
3.1 Charge/exchange starter battery.
Proceed according to battery manufacturer instructions.
4.1 Exchange DC fuse (Fuse for the fuel pump) - see wiring scheme
Exchange the relevant fuses at the generators’ terminal block.
A defective fuse is not always visually detectable. Measure the fuse with a multimeter for connecting passage.
4.2 Correct mounting/connection of the fuel pump.
Check the appropriate polarity at the connections and the tight fit of the connections at the fuel pump.
4.3 Exchange fuel pump.
Loosen the electric connections of the fuel pump.
Loosen the holding screws of the fuel pump.
Mount the new fuel pump in reversed order.
5.1 Remove buckling from the fuel hose.
Remove any buckling and improve the installation to avoid further disruptions.
5.2 Sealing the connections.
Seal the system in an appropriate way. The system has to be checked for leakage at frequent intervals.
5.3 Ventilating the fuel system.
Ventilate the fuel system as stated in the chapter ’Installation’. If air keeps entering into the fuel system, this might be
an indication for a leaking connection or porose hoses. Then the fuel system should be inspected by a professional.
5.4 Refuelling
Refuel your vehicle/the generator as described in the bord manual.