e398
PPC4000 FAULT
"User Output data" is corrupted
Pressing RESET will restore values from stored
memory
e399
PPC4000 FAULT
"CO Setup data" is corrupted
Pressing RESET will restore values from stored
memory
e400
to
e419
Unused
Unused
e420
SERVO FAULT
Manual move button pressed on servo 1
Inspect Servo for button
obstruction (wires touching)
e421
SERVO FAULT
Manual move button pressed on servo 2
Inspect Servo for button
obstruction (wires touching)
e422
SERVO FAULT
Manual move button pressed on servo 3
Inspect Servo for button
obstruction (wires touching)
e423
SERVO FAULT
Manual move button pressed on servo 4
Inspect Servo for button
obstruction (wires touching)
e424
SERVO FAULT
Manual move button pressed on servo 5
Inspect Servo for button
obstruction (wires touching)
e425
SERVO FAULT
Manual move button pressed on servo 6
Inspect Servo for button
obstruction (wires touching)
e426
SERVO FAULT
Manual move button pressed on servo 7
Inspect Servo for button
obstruction (wires touching)
e427
SERVO FAULT
Manual move button pressed on servo 8
Inspect Servo for button
obstruction (wires touching)
e428
SERVO FAULT
Manual move button pressed on servo 9
Inspect Servo for button
obstruction (wires touching)
e429
SERVO FAULT
Manual move button pressed on servo 10
Inspect Servo for button
obstruction (wires touching)
e430
to
e522
Unused
Unused
e523
PPC4000 FAULT
Invalid Sequencing Data