86
Error Code
Displayed
Reason for error
Possible remedy
e16
NO FUEL SERVO
The user has no servo in the current profile with one of
these names: FU1,FU2,GAS,OIL,CUP,PUM,WAS,PRI
Name one servo in current profile as a fuel servo
e17
INVALID SETPOINT
User has not configured setpoint 2 to be using
sensor 1
Configure setpoint 2 to use sensor 1
e18
Unused
Unused
e19
SENSOR 1 MARGINAL
SENSOR 1 has reached user defined marginal setting
This could be normal operation
e20
SENSOR 1 MARGINAL
SENSOR 1 has reached user defined marginal setting
This could be normal operation
e21
SENSOR 2 MARGINAL
SENSOR 2 has reached user defined marginal setting
This could be normal operation
e22
SENSOR 2 MARGINAL
SENSOR 2 has reached user defined marginal setting
This could be normal operation
e23
SENSOR 2 MARGINAL
SENSOR 2 has reached user defined marginal setting
This could be normal operation
e24
SENSOR 3 MARGINAL
SENSOR 3 has reached user defined marginal setting
This could be normal operation
e25
SENSOR 3 MARGINAL
SENSOR 3 has reached user defined marginal setting
This could be normal operation
e26
SENSOR 3 MARGINAL
SENSOR 3 has reached user defined marginal setting
This could be normal operation
e27
SENSOR1 HIGH LIMIT
SENSOR 1 has reached user defined limit setting
This could be normal operation
e28
SENSOR1 HIGH LIMIT
SENSOR 1 has reached user defined limit setting
This could be normal operation
e29
SENSOR2 HIGH LIMIT
SENSOR 2 has reached user defined limit setting
This could be normal operation
e30
SENSOR2 HIGH LIMIT
SENSOR 2 has reached user defined limit setting
This could be normal operation
e31
SENSOR2 HIGH LIMIT
SENSOR 2 has reached user defined limit setting
This could be normal operation
e32
SENSOR3 HIGH LIMIT
SENSOR 3 has reached user defined limit setting
This could be normal operation
e33
SENSOR3 HIGH LIMIT
SENSOR 3 has reached user defined limit setting
This could be normal operation
e34
SENSOR3 HIGH LIMIT
SENSOR 3 has reached user defined limit setting
This could be normal operation
e35
SENSOR1 UNDER RNG
SENSOR 1 input is under 2mA
Defective sensor or check wiring
e36
SENSOR1 OVER RNG
SENSOR 1 input is over 22mA
Defective sensor or check wiring
e37
SENSOR2 UNDER RNG
SENSOR 2 input is under 2mA
Defective sensor or check wiring
e38
SENSOR2 OVER RNG
SENSOR 2 input is over 22mA
Defective sensor or check wiring
e39
SENSOR3 UNDER RNG
SENSOR 3 input is under 2mA
Defective sensor or check wiring
e40
SENSOR3 OVER RNG
SENSOR 3 input is over 22mA
Defective sensor or check wiring
e41
Z BOARD
Z Board internal error
Replace Z Board
e42
Z BOARD
Z Board internal error
Replace Z Board
e43
PPC4000 FAULT
PPC4000 Internal Error
Replace PPC4000 (notify Fireye about this error)
e44
PPC4000 FAULT
PPC4000 Internal Error
Replace PPC4000 (notify Fireye about this error)
e45
PPC4000 FAULT
PPC4000 Internal Error
Replace PPC4000 (notify Fireye about this error)
e46
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e47
O2 FAULT
O2 is not communicating with the PPC4000
Check Wiring or add 200 Ohm resistor
e48
O2 FAULT
O2 Probe is reporting that the O2 level is below the user
configured minimum
This could be normal operation
e49
O2 FAULT
O2 Probe is reporting that the O2 level is above the user
configured maximum
This could be normal operation