15
The PPC4000 is mounted to the cabinet back plate using 4 X #8-32 screws. Following the mounting
dimensions shown in Figure 4, drill and tap 4 mounting holes. Firmly screw the control to the cabinet
back plate.
WIRING CONNECTIONS
Terminal
Type
Description
Rating/wiring
P3.1
L1
Line Voltage Supply
120/230 VAC (+10%, -15%) 50/60 Hz
P3.2
L2/N
Line Voltage Common
EARTH (stud)
Protective Earth
Chassis ground connection
P4.1
Input
Alarm Relay Input
Voltage free contacts
P4.2
Output
Alarm Relay Output
Voltage free contacts, 3A 250VAC
P4.3
Input
Operating Control Input
Connect to recycle limits In
P4.4
Output
Operating Control Output
Connect to recycle limits Out, 16A
250VAC
P2.1
Power
O2 Probe & User Interface Power
24 VDC, 59-562 - RED
P2.2
Power
Servo Power, uC controlled
24 VDC, 59-565 - RED
P2.3
Power
Servo Power, uC controlled
24 VDC, 59-565 - RED
P2.4
Common
O2, User Interface, Servo VDC Return 0 VDC, 59-562 - BLACK
P2.5
Common
O2, User Interface, Servo VDC Return 0 VDC, 59-565 - BLACK
P2.6
Common
O2, User Interface, Servo VDC Return 0 VDC, 59-565 - BLACK
P11.1
Common
0 VDC
VDC Return
P11.2
Power
Temp/Pressure Source Voltage
24 VDC Nominal (class 2)
P11.3
Power
Temp/Pressure Source Voltage
24 VDC Nominal (class 2)
P11.4
Common
0 VDC
VDC Return
P11.5
Output
Analog Output
4-20mA output
P11.6
Input
SENS 5 Sensor Analog Input
See Table 2 for sensor type, range
and settings
P11.7
Input
SENS 4 Sensor Analog Input
P11.8
Input
SENS 3 (AUX2) Sensor Analog Input
P11.9
Input
SENS 2 (AUX1) Sensor Analog Input
P11.10
Input
SENS 1 (PCV) Sensor Analog Input
P11.11
Common
0 VDC
VDC Return
P12.1
Modbus-RTU A
P12.2
Modbus-RTU B
P12.3
SEQUENCING A
P12.4
SEQUENCING B
P12.5
Servo Comms A1
59-565, ORANGE
P12.6
Servo Comms B1
59-565, BROWN
P12.7
User Interface, Tx
59-562, YELLOW
P12.8
User Interface, Ty
59-562,BLUE
P12.9
User Interface, Rb
59-562, BROWN
P12.10
User Interface, Ra
59-562, ORANGE
P12.11
O
2
Comms A1
59-565, ORANGE
P12.12
O
2
Comms B1
59-565, BROWN