14
PPC4000 INSTALLATION
Install the PPC4000 control where the relative humidity never reaches the saturation point. The
Nexus PPC4000 system is designed to operate in a maximum 85% relative humidity continuous,
non-condensing environment. Do not install the PPC4000 system where it can be subjected to vibra-
tion in excess of 0.5G continuous maximum vibration. The PPC4000 system is not a weather tight
enclosure. The standard vertical position is recommended. Allow at least one inch clearance around
the control for service and installation.
Refer to Figure 4 for mounting dimensions.
FIGURE 4.
Mounting Dimensions
7.56”
192mm
4.31”
109.5mm
.38”
9.5mm
5.06”
128.5mm
.38”
9.5mm
.25”
6.4mm
8.06”
204.7mm
.25”
6.4mm
TAP FOR 8-32 SCREW
BASE PLATE OUT LINE