87
Error Code
Displayed
Reason for error
Possible remedy
e50
O2 FAULT
O2 Probe is reporting that the stack temperature is
below the user configured minimum
This could be normal operation
e51
O2 FAULT
O2 Probe is reporting that the stack temperature is
above the user configured maximum
This could be normal operation
e52
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e53
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e54
O2 FAULT
O2 thermocouple is disconnected or defective
Check thermocouple for breakage or replace it
e55
O2 FAULT
O2 stack temperature is above the user configurable
temperature or thermocouple is defective
This could be normal operation
e56
O2 FAULT
O2 stack temperature is below 0 Celsius or
thermocouple is defective
This could be normal operation
e57
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e58
O2 FAULT
O2 probe temperature is above 85 Celsius
Check O2 Probe fan
e59
O2 FAULT
O2 probe temperature is below -25 Celsius
This could be normal operation if it is really cold
e60
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e61
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e62
O2 FAULT
O2 Probe PPC4000 FAULT
Replace O2 Probe
e63
O2 FAULT
The 24V supply to the O2 probe is under
Measure supply voltage at the probe
e64
O2 FAULT
The 24V supply to the O2 probe is over
Measure supply voltage at the probe
e65
O2 FAULT
O2 Probe 12V supply open
Replace O2 Probe
e66
O2 FAULT
O2 Probe 12V supply low
Replace O2 Probe
e67
O2 FAULT
O2 Probe 12V supply high
Replace O2 Probe
e68
O2 FAULT
O2 Probe unexpected calibration fault
Replace O2 Probe cartridge
e69
O2 FAULT
O2 Probe stuck
Replace O2 Probe cartridge
e70
O2 FAULT
O2 Probe calibration needed
This could be normal operation
e71
O2 FAULT
O2 Probe heater shorted
Replace O2 Probe cartridge
e72
O2 FAULT
O2 Probe heater open
Replace O2 Probe cartridge
e73
O2 FAULT
O2 Probe pump short
Replace O2 Probe cartridge
e74
O2 FAULT
O2 Probe pump open
Replace O2 Probe cartridge
e75
O2 FAULT
O2 Probe nernst cell short
Replace O2 Probe cartridge
e76
O2 FAULT
O2 Probe nernst cell open
Replace O2 Probe cartridge
e77
O2 FAULT
O2 Probe conversion timeout
Replace O2 Probe cartridge
e78
O2 FAULT
O2 Probe low voltage
Replace O2 Probe cartridge
e79
O2 FAULT
O2 Probe too cold
This could be normal operation
e80
O2 FAULT
O2 Probe too hot
Replace O2 Probe cartridge
e81
O2 FAULT
O2 Probe air calibration
Replace O2 Probe cartridge
e82
O2 FAULT
O2 Probe heater calibration
Replace O2 Probe cartridge
e83
O2 FAULT
O2 Probe comm busy
Replace O2 Probe cartridge
e84
O2 FAULT
O2 Probe comm fault
Replace O2 Probe cartridge
e85
O2 FAULT
O2 Probe Sensor warming up
This could be normal operation
e86
O2 FAULT
O2 Probe sensor in standby
Replace O2 Probe cartridge
e87
Unused
Unused
e88
PPC4000 FAULT
PPC4000 Internal Error
Replace PPC4000 (notify Fireye about this error)