Document #50193 Rev. E 01/30/02 P/N 50193:E
75
Central Station Communications
The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the
reporting structure for all formats.
Refer to Table 4-2 for an explanation of each letter code in Table 4-1 .
Refer to Table 4-3 for a list of compatible receivers.
TABLE 4-1:
Format Selection Addresses (16+42) Programming Level 1
Format #
0, 2, 4, 6, 8
Format #
3, 5, 7, 9
Format #
1, A, C
Format #
B, D
Report
3+1/4+1/Standard
4+1 Express
3+1/4+1/Expanded
4+2/Standard
4+2 Express
4+2/Expanded
Alarm
SSS(S) A
SSS(S) A
AAA(A) Z
SSSS AA2
SSSS AZ
Alarm Restore
SSS(S) RA
SSS(S) RA
RARARA(RA) Z
SSSS RARA2
SSSS RAZ
Zone Trouble
(Zone Open)
SSS(S) TZ
SSS(S) TZ
TZTZTZ(TZ) Z
SSSS TZTZ2
SSSS TZZ
Zone Trouble Restore
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSSS RTZRTZ2
SSSS RTZZ
System Trouble
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2
SSSS TSY
System Trouble Restore
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2
SSSS RTSY
Zone Disable
SSS(S) DZ
SSS(S) DZ
DZDZDZ(DZ) Z
SSSS DZDZ2
SSSS DZZ
Zone Disable Restore
SSS(S) RDZ
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
SSSS RDZRDZ2
SSSS RDZZ
Bell Disable
SSS(S) DB
SSS(S) DB
SSSS DBDB2
SSSS DBDB2
Bell Disable Restore
SSS(S) RB
SSS(S) RB
SSSS RBRB2
SSSS RBRB2
Low Battery
SSS(S) L
SSS(S) L
SSSS LL2
SSSS LL2
Low Battery Restore
SSS(S) RL
SSS(S) RL
SSSS RLRL2
SSSS RLRL2
No Battery
SSS(S) N
SSS(S) N
SSSS NN2
SSSS NN2
No Battery Restore
SSS(S) RN
SSS(S) RN
SSSS RNRN2
SSSS RNRN2
AC Loss
SSS(S) P
SSS(S) P
SSSS PP2
SSSS PP2
AC Loss Restore
SSS(S) RP
SSS(S) RP
SSSS RPRP2
SSSS RPRP2
Fire Drill
SSS(S) Fd
SSS(S) Fd
SSSS FdFd2
SSSS FdFd2
Fire Drill Restore
SSS(S) RFd
SSS(S) RFd
SSSS RFdRFd2
SSSS RFdRFd2
Supervisory Condition
SSS(S) V
SSS(S) V
VVV(V) Z
SSSS VV2
SSSS VZ
Supervisory Condition
Restore
SSS(S) RV
SSS(S) RV
RVRVRV(RV) Z
SSSS RVRV2
SSSS RVZ
Test Report
SSS(S) X
SSS(S) X
SSSS XX2
SSSS XX2
Up or Download
SSS(S) UD
SSS(S) UD
SSS UDUD2
SSS UDUD2
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...