Operation
72
Document #50193 Rev.E 01/30/02 P/N 50193:E
4.3.7 Process Monitored Alarm Response
Upon detection of a critical or noncritical process monitored alarm condition on any zone, the control panel will:
• Display the alarm message
PAXX
(where XX = zone number)
• Communicate the alarm code programmed for the activated zone
• Store the alarm in the History File
• Pulse the piezo sounder at a ¼ second On, ¼ second Off
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for process alarm activation
• Output alarm message to printer
• Terminate upload or download communications
• Blink all remote annunciator zone alarm LEDs (¼ second On, ¼ second Off)
4.3.8 Process Monitored Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset switch has been pressed
(process monitored alarm devices reset). The control panel will perform the following upon restoral of all active pro-
cess monitored alarms:
• Clear the 4-character display
• Communicate the alarm restoral code programmed for the activated zone
• Store the alarm restoral message in the History File
• Turn off the piezo sounder
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for process alarm activation
• Output alarm restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator zone alarm LEDs
Note that for any zone programmed for autoresettable process monitored alarm, the reset key does not need to be
pressed to clear the zone.
4.3.9 OFF Normal Reporting
Removing the panel from Normal Mode and placing it into Troubleshoot, Walktest or Program Mode causes a trans-
mission of an 'off normal' fault message. Returning the panel to Normal Mode causes a transmission of a 'return to
normal' restoral message.
4.3.10 Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. While in Normal Mode or Walktest Mode,
zones may be disabled if they are normal, in trouble or alarmed.
If the panel is in alarm, the silence switch must be
pressed first before zone disable will function in Normal Mode.
To disable a zone, press the
MODE
key once, (the display will go blank). You then have 10 seconds to start entering
the code
3472
. Next, press the
[ENTER/STORE]
key.
☛
3472
spells DISA on a Touch-Tone
®
phone.
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...