Central Station Communications
76
Document #50193 Rev.E 01/30/02 P/N 50193:E
Note that for Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number,
and the second digit corresponding to any system trouble condition. Only the first digit is programmable.
TABLE 4-2:
Format Selection Address Explanation
Where:
SSS or SSSS
= Subscriber ID
A
= Alarm (1st digit)
A2
= Alarm (2nd digit)
Z
= Zone Number
RA
= Alarm Restore (1st digit)
RA2
= Alarm Restore (2nd digit)
TZ
= Zone Trouble (1st digit)
TZ2
= Zone Trouble (2nd digit)
RTZ
= Zone Trouble Restore (1st digit)
RTZ2
= Zone Trouble Restore (2nd digit)
TS
= System Trouble (1st digit)
TS2
= System Trouble (2nd digit)
RTS
= System Trouble Restore (1st digit)
RTS2
= System Trouble Restore (2nd digit)
DZ
= Zone Disable (1st digit)
DZ2
= Zone Disable (2nd digit)
RDZ
= Zone Disable Restore (1st digit)
RDZ2
= Zone Disable Restore (2nd digit)
DB
= Bell Disable (1st digit)
DB2
= Bell Disable (2nd digit)
RB
= Bell Disable Restore (1st digit)
RB2
= Bell Disable Restore (2nd digit)
L
= Low Battery (1st digit)
L2
= Low Battery (2nd digit)
RL
= Low Battery Restore (1st digit)
RL2
= Low Battery Restore (2nd digit)
N
= No Battery (1st digit)
N2
= No Battery (2nd digit)
RN
= No Battery Restore (1st digit)
RN2
= No Battery Restore (2nd digit)
P
= AC Loss (1st digit)
P2
= AC Loss (2nd digit)
RP
= AC Loss Restore (1st digit)
RP2
= AC Loss Restore (2nd digit)
FD
= Fire Drill (1st digit)
FD2
= Fire Drill (2nd digit)
RFD
= Fire Drill Restore (1st digit)
RFD2
= Fire Drill Restore (2nd digit)
V
= Supervisory Condition (1st digit)
V2
= Supervisory Condition (2nd digit)
RV
= Supervisory Condition Restore (1st digit)
RV2
= Supervisory Condition Restore (2nd digit)
X
= Test Report (1st digit)
X2
= Test Report (2nd digit)
Y
= A Trouble corresponding to the following:
1 = Earth Fault
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = NAC #1 Fault
7 = NAC #2 Fault
8 = NAC #3 Fault
9 = NAC #4 Fault
A = Communication Failure to Primary Number
B = Communication Failure to Secondary Number
C = Printer Fault
D = Annunciator Fault
E = 485 Communication Failure
F = System Off Normal
UD
= Upload/Download (1st digit)
UD2
= Upload/Download (2nd digit)
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...