Program Options
44
Document #50193 Rev.E 01/30/02 P/N 50193:E
Make/Break Ratio for Primary Phone (59)
Use this address only if you have chosen '1' for address 58. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (60)
A '0' programmed in this address by the factory triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (61)
Use this address only if you have chosen '1' for address 60. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is a 62/38 ratio.
Address (62)
Leave entry as default of '0'.
Address (63)
Leave entry as default of '0'.
Zones 1 through 10 Function Selection (64-73)
The ten zones on the control panel may be programmed as shown in Table 3-1 . Program entries alter zone func-
tion, transmittal priority and, as a result of altering the zone definition, the transmitted event code message is auto-
matically changed. Remote switch entries 9, A, B and C cause the zone function to be altered to match the FACP
keypad entries. Initial closure (or shorting) of a switch causes the switch function to occur. The switch must be
returned to its normal position.
Zone 1 Function Selection (64)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
TABLE 3-1:
Zone Functions
Program Entry
Function
0
Operate 2-wire smoke detectors
1
Pull Station
2
Normally-Open Contact Device (heat detector, 4-wire smoke, etc.)
3
Supervisory
4
Supervisory, autoresettable. Self restore function, is not latched by the control panel
5
Waterflow, silenceable. Silencing of Silenceable Notification Appliance Circuits allowed
6
Waterflow, nonsilenceable. Silencing of Silenceable Notification Appliance Circuits not
allowed. Must clear waterflow alarm condition and press reset key
7
Critical and noncritical process monitoring
8
Autoresettable process monitoring
9
Remote reset switch
1
1. For remote switch applications, use Fire•Lite P/N: AKS-1F or equivalent UL listed switch.
A
Remote silence switch
1
B
Remote acknowledge switch
1
C
Remote manual evacuate (drill) switch
1
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...