History Mode
80
Document #50193 Rev.E 01/30/02 P/N 50193:E
To return the control panel to Normal Mode, press the
MODE
key followed by the 4- digit code
6676
and then the
[ENTER/STORE]
key. To go to any other mode, press the
MODE
key followed by the appropriate 4-digit code and
then the
[ENTER/STORE]
key. To go from silent walktest to audible walktest (or vice versa), press the
MODE
key
followed by the
[ENTER/STORE]
key.
S__0
or
S__1
will appear in the display. Simply alter the '0' or '1' entry then
press the
[ENTER/STORE]
key. Any delay between key entries greater than 10 seconds causes the control panel to
remain in Walk Test Mode.
The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes.
This would include pressing any keys or activity on any zone. Exiting Walk Test Mode leaves the Walk Test file in
memory such that it may be printed in Print Mode. Subsequent entries into Walk Test Mode will delete the Walk Test
file.
During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activa-
tion), subsequent testing of devices on the same zone will not trigger the NACs. Be certain to reset or clear each
device after testing.
Note that remote site upload or download is possible when the system is in Walk Test Mode.
5.2
History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character dis-
play or via an optional printer. See the following page for a list and description of each event displayed.
This History File list is a first-in, first-out (FIFO) buffer. Only the most recent events may be called up from memory.
Old events will be overwritten, i.e. pushed out of the FIFO. The number of stored events is 256. The History File is
kept in E
2
memory. Complete power loss will not erase the list.
Pressing the
MODE
key followed by the 4-digit code
4478
and then the
[ENTER/STORE]
key places the control
panel into History Mode. The most recent event will be displayed.
This will not occur if there are any active alarm
conditions present. The fire protection remains active in History Mode. If an alarm occurs, the panel will automati-
cally exit History Mode.
☛
4478
spells HIST on a Touch-Tone
®
phone.
Once in History Mode, the control panel will:
• Display all events as they occurred since the last time the History File list was cleared (the most recent event
being displayed first)
• Ignore all keys except those mentioned in this section
• Continue to communicate any events not previously acknowledged at the Central Station prior to entering
History Mode.
The Down arrow key moves the History File to show older (previous) events. The Up arrow key moves the History
File to show newer (most recent) events.
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...