Document #50193 Rev. E 01/30/02 P/N 50193:E
45
Program Options
Zone 2 Function Selection (65)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 3 Function Selection (66)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 4 Function Selection (67)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 5 Function Selection (68)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 6 Function Selection (69)
Factory default for zone 6 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 7 Function Selection (70)
Factory default for zone 7 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 8 Function Selection (71)
Factory default for zone 8 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 9 Function Selection (72)
Factory default for zone 9 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...