Document #50193 Rev. E 01/30/02 P/N 50193:E
19
Optional Accessories
LED-10 Series Annunciator (LED Zone Type Annunciator)
The LED-10 Series is a 10 zone LED annunciator which mounts on a 3-gang electrical box and provides LED
indication of the following:
• Alarm Zones 1 through 10
• Trouble Zones 1 through 10
• AC Power (green)
• System Alarm (red)
• System Trouble (yellow)
• System Supervisory (yellow)
• Alarm Silence (yellow)
A local trouble sounder and switches for remote Acknowl-
edge, Silence, Drill and Reset are also provided. Wiring is
inherently supervised by the FACP. Slide-in paper labels
permit an easy change of zone information. DIP switches
allow the enabling and disabling of the local piezo sounder
(with approval of local AHJ), enabling and disabling of the
mechanical keyswitch which may be used to prevent unau-
thorized use of the function switches and selection of
annunciator receive/transmit mode (Refer to Figure 2-15 on
page 35).
Note that the LED-10 Series Remote Annunciator requires the use of the LED-10IM Interface Module.
ACS Series Annunciators (LED Zone Type)
The ACS Series Annunciators remotely display system status. The annunciators display zone alarm and trouble
status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The ACS Series
Annunciators require the use of the LED-10IM Interface Module. For more detailed information, refer to the
appropriate annunciator manual.
✓
ACM-16ATF
- The Annunciator Control Module-16ATF
contains 16 red alarm and 16 yellow trouble LEDs, a system trou-
ble LED, an ON LINE/POWER LED and a local piezo sounder
with switches for Acknowledge, Silence, Reset and Drill. The
ACM-16ATF has rotary address switches and will accept up to 3
AEM-16ATF Expanders. The ACM-16ATF can be mounted in a
Fire•Lite ABS-1F or ABF-1F backbox. Refer to the
ACM-16ATF Manual for detailed information.
Note that only
one ACM-16ATF is required to annunciate 10 zones of alarm and
trouble, provided '8 Point Shift' function is selected. Refer to
Annunciator Manual P/N 51480 for additional information.
✓
AEM-16ATF
- The Annunciator Expander Module-16ATF con-
nects to the ACM-16ATF and adds 16 sets of red alarm LEDs and
yellow trouble LEDs. Up to three AEM-16ATFs may be added to
an ACM-16ATF but only one is required.
Note that one
AEM-16ATF is required with an ACM-16ATF to annunciate 10
zones of alarm and trouble as well as general system status pro-
vided '8 Point Shift' function is not selected. Refer to Annunciator
Manual P/N 51480 for additional information.
FIGURE 1-6:
LED-10 Series Annunciator
FIGURE 1-7:
ACM-16ATF
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...