Document #50193 Rev. E 01/30/02 P/N 50193:E
89
Downloading Initiated at a Service Terminal
Once the called Service Terminal accepts the incoming call (control panel) and verifies the secret code, the download-
ing process is allowed to continue. Downloading progresses until all programmed information has been successfully
loaded into the control panel. Communication terminates upon the Service Terminal hanging up or upon the FACP
hanging up after a two minute time-out following completion of data transfer.
6.3
Downloading Initiated at a Service Terminal
Before initiating the Download procedure, make certain that the communicator is in the standby state; red Line Seize,
green Modem and green Kissoff LEDs are off.
Once an incoming call is accepted/answered by the control panel, the panel will:
1.
Establish basic modem connection
2.
Verify secret code
3.
Verify callback vs. no callback request from the Service Terminal (if callback is requested, panel will perform
steps 4 through 10; if no callback is requested, panel will perform only steps 9 and 10)
4.
Identify the Service Terminal location
5.
Hang-up/disconnect call
6.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
this message is accepted, the control panel will proceed to the next step
7.
Return call to Service Terminal
8.
Verify secret code
9.
Begin downloading
10.
Upon completion of download, call-back Central Station(s) and report a successful download or failed upload/
download status (if programmed to do so)
6.4
Uploading Initiated at a Service Terminal
Items that may be uploaded from the control panel to a Service Terminal include:
• All or portions of programmed data plus the real-time clock, time and date
• Entire Walk Test data file in real-time continuous or as a 'snapshot'
• Troubleshoot system voltages in real-time continuous or as a 'snapshot'
• Entire 256 event History File
• Current system status in real-time continuous or as a 'snapshot'
Uploading is possible at any time provided the following conditions are true:
✓
The control panel may be in any mode of operation. Uploading is not possible if the communicator is
active or while testing the phone lines while in Troubleshoot Mode
✓
There cannot be any active communications ongoing with the Central Station receiver
✓
All active events must be successfully 'kissed-off' by the Central Stations (communicator must be in a
standby state with no new information waiting to be transmitted to a Central Station).
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...