Digital Communicator
30
Document #50193 Rev.E 01/30/02 P/N 50193:E
2.6
Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made
possible via double line seizure as well as usage of an RJ31X style interconnection.
It is critical that the panel's dig-
ital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone
lines is required as shown in Figure 2-8.
FIGURE 2-8:
Wiring Phone Jacks
Primary Lines - Incoming
Telco Phone Lines
Secondary Lines - Incoming
Telco Phone Lines
Ring
Ring
Ring
Ring
Tip
Tip
Tip
Tip
Green Wire
Green Wire
Red Wire
Red Wire
To premise phones
To premise phones
Note: Shorting bars
inside RJ31X Jack
removed during male
plug insertion
7 foot (2.13 m)
cables (MCBL-7)
not supplied -
order separately
Primary Phone Line PH1
Secondary Phone Line PH-2
Modular
Female
Connectors
Male Plug Connectors
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...