Operation
70
Document #50193 Rev.E 01/30/02 P/N 50193:E
4.3.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset switch has been pressed
(pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The con-
trol panel will perform the following upon restoral of all active alarms:
• Turn off the FACP alarm LED
• Clear the 4-character display
• Send all 'Zone Restoral' messages to the Central Station
• Turn off the Notification Appliance Circuits
• Turn off the piezo sounder
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for alarm activation
• Output alarm restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator general alarm LEDs
• Turn off all remote annunciator zone alarm LEDs
4.3.3 System Supervisory Condition Response
Program zones for Supervisory in applications where a waterflow sensing device has been employed and the wiring
to the waterflow valve and/or a tamper switch is to be monitored. If the tamper switch has been activated (Normally
Open contacts close), a supervisory alarm condition will occur.
When a supervisory condition occurs, the control panel will cause the following:
• Blink the FACP supervisory LED (½ second On, ½ second Off)
• Display the following message: SUXX (XX=Zone Number)
• Communicate the supervisory condition to the Central Station
• Store the 'supervisory' message in the History File
• Pulse system piezo sounders (½ second On, ½ second Off)
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for supervisory activation
• Output system supervisory message to printer
• Terminate upload or download communications
• Blink all remote annunciator general supervisory alarm LEDs (½ second On, ½ second Off)
• Blink all remote annunciator zone supervisory alarm LEDs (½ second On, ½ second Off)
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the
control panel will perform the following:
• Turn off the supervisory LED
• Clear the display of the 'SUXX'
• Communicate a supervisory restoral message to the Central Station
• Shut off system piezo sounders
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for supervisory activation
• Output system supervisory restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator general supervisory alarm LEDs
• Turn off all remote annunciator zone supervisory alarm LEDs
Note that for any zone programmed for Supervisory autoresettable, the Reset key does not need to be pressed to clear
the zone (supervisory condition).
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...