Document #50193 Rev. E 01/30/02 P/N 50193:E
97
Main Panel Options Program Sheets
Main Panel Options Programming Sheets (Factory Default Settings)
---To enter Programming Level 1, press the
MODE
key,
7764
, '1',
[ENTER/STORE]
❏
00
❏
01
❏
02
❏
03
❏
04
❏
05
❏
06
❏
07
❏
08
❏
09
❏
10
❏
11
❏
12
❏
13
❏
14
❏
15
Addresses 00 to 15 store the Primary Central Station Phone Number.
Enter 'F' to represent the end of number.
❏
16
Primary Central Station Communication Format:
('E' for Ademco Contact ID Format).
❏
17
❏
18
❏
19
❏
20
Primary Central Station Account Code
.
❏
21
❏
22
❏
23
❏
24
Primary Central Station 24-Hour Test Time.
0000 = 12:00 midnight.
❏
25
Primary Central Station Number Test Time Interval. '0' for 24-hour.
❏
26
❏
27
❏
28
❏
29
❏
30
❏
31
❏
32
❏
33
❏
34
❏
35
❏
36
❏
37
❏
38
❏
39
❏
40
❏
41
Addresses 26 to 41 store the Secondary Central Station Phone Number.
Enter 'F' to represent the end of number.
❏
42
Secondary Central Station Communication Format: (
'E' for Ademco Contact ID Format).
❏
43
❏
44
❏
45
❏
46
Secondary Central Station Account Code
.
❏
47
❏
48
❏
49
❏
50
Secondary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
❏
51
Secondary Number Test Time Interval. '0' for 24-hour.
❏
52
Alarm Presignal. '0' for no alarm presignal.
❏
53
❏
54
❏
55
Alarm Presignal Delay Time. 120 second alarm presignal delay.
❏
56
Communicator/Fire Panel Selection. '0' for panel only operation.
❏
57
Backup Reporting. '0' to report to Secondary Central Station phone # as backup only.
❏
58
Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
❏
59
Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.
❏
60
Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
❏
61
Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio.
❏
62
Future use. Leave default of '0'.
❏
63
Future use. Leave default of '0'.
❏
64
Zone 1 Function Select. '0' for 2-wire smoke detectors.
❏
65
Zone 2 Function Select. '0' for 2-wire smoke detector.
❏
66
Zone 3 Function Select. '0' for 2-wire smoke detectors.
F F F F F F F F F F F F F F F F
E
0 0 0 0
0 0 0 0
0
F F F F F F F F F F F F F F F F
E
0 0 0 0
0 0 0 0
0
0
1 2 0
0
0
0
0
0
0
0
0
0
0
0
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...