Document #50193 Rev. E 01/30/02 P/N 50193:E
69
Operation
4.3
Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When
no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED).
The Notification Appliance Circuits will be off, all relays are in their normal state, the onboard piezo sounder will be
off and the printer (if connected) will not be printing. The Primary and Secondary Phone Line Active LEDs are off
since the communicator is not active.
All alarm and system trouble conditions are annunciated on the control panel's display. The control panel will main-
tain an 'active event list' which will consist of all alarms, supervisory alarms and system troubles currently active and
not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be
blank. All alarms and troubles are stored in a history file and may be recalled at any time.
Higher priority events take precedence over lower priority events. Display and reporting of System Status is done on
a priority basis. Priorities are, from highest to lowest:
1.
Alarms
2.
Supervisory Alarms
3.
System Troubles
4.
Process Monitoring Alarms
If the events to be displayed consist of alarms and disabled zones only (no troubles), the control panel will scroll them
on the display. As each new alarm occurs, it will be displayed immediately on the display for five seconds. After this
five second period, the display will scroll all alarms in the system. Pressing the 1st Event key or one of the 'ACK'
keys will stop the scrolling. The 1st Event key will also cause the display to show the
First
alarm that occurred after
the panel was last reset, cleared of all active events and placed into normal mode. Operation of the Up and Down
arrow keys will display all remaining events in sequence.
If events to be displayed include system troubles, only one event is displayed at a time and there is no scrolling. The
event displayed is the highest priority. Pressing the 1st Event key will cause the display of the first event that occurred
after the panel was last reset, cleared of all active events and placed into normal mode. Operation of the Up and Down
arrow keys will display all remaining events in order of their occurrences.
4.3.1 Fire Alarm Response
The control panel will, upon detection of an alarm condition, cause the following:
• Blink the FACP alarm LED (1 second On, 1 second Off)
• Display the alarm message (i.e.
A__1
Alarm on Zone 1)
• Communicate the alarm to the Central Station
• Store the alarm in the History File
• Turn the Notification Appliance Circuits on
• Turn the piezo sounder on steady
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for alarm activation
• Output alarm message to printer
• Terminate upload or download communications
• Blink all remote annunciator general alarm LEDs (1 second On, 1 second Off)
• Blink all remote annunciator zone alarm LEDs (1 second On, 1 second Off)
Note that when any zone is programmed as a supervisory or process monitored zone, it will not be processed in the
same manner as a conventional alarm zone. Refer to
“System Supervisory Condition Response” on page 70 and
“Process Monitored Alarm Response” on page 72.
Содержание MS-5210UD
Страница 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...
Страница 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...
Страница 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...
Страница 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...