4. Commissioning
4-71
Festo P.BE-SBO-Q-EN en 1602e
Telnet commands
WFW – Write FlagWord
WFW <address, value>
Writes a value to the flag word address specified
(
è
The following example writes the value 5 to the flagword
address 33 (fast access to check program preselection).
Fig. 4/20: Writing to a flagword address
In case of fault, the response is with an error code and error
message.
Note
Use only integers when writing values on flagword
addresses.
RFW – Read FlagWord
RFW <address>
Outputs the current value of the specified flag word address
as text (
è
With this command, up to 64 addresses can be read out. Here
the flag word addresses should be separated by commas:
RFW <address1, address2, address3, ...> .
Fig. 4/21: Reading out flag word addresses
Содержание SBO***-Q Series
Страница 2: ......
Страница 19: ...System overview 1 1 Festo P BE SBO Q EN en 1602e Chapter 1 System overview...
Страница 39: ...Mounting 2 1 Festo P BE SBO Q EN en 1602e Chapter 2 Mounting...
Страница 47: ...Installation 3 1 Festo P BE SBO Q EN en 1602e Chapter 3 Installation...
Страница 62: ...3 Installation 3 16 Festo P BE SBO Q EN en 1602e...
Страница 63: ...Commissioning 4 1 Festo P BE SBO Q EN en 1602e Chapter 4 Commissioning...
Страница 162: ...4 Commissioning 4 100 Festo P BE SBO Q EN en 1602e Fig 4 34 Structure of an imported data type...
Страница 175: ...Diagnostics and error handling 5 1 Festo P BE SBO Q EN en 1602e Chapter 5 Diagnostics and error handling...
Страница 183: ...Technical appendix A 1 Festo P BE SBO Q EN en 1602e Appendix A Technical appendix...
Страница 247: ...Index B 1 Festo P BE SBO Q EN en 1602e Appendix B Index...
Страница 248: ...B Index B 2 Festo P BE SBO Q EN en 1602e Table of contents B Index B 1...