Chapter 7 Elevator Application Guidance
MONT72 Series User Manual V1.0
- 75 -
7.1.3
Inspection Running
Before inspection running
1
After motor parameter auto-tuning, motor output U / V / W connections and encoder connection are not
changed.
2
Set F03.06 (Inspection Acc. speed) and F03.07 (Inspection Dec. speed).
Inspection running
1
If the actual running direction of motor is not the command direction, set F00.08 (Run direction) = 1.
2
Make sure that the motor can run normally.
3
Make sure the motor can run normally and the signals of the brake and power circuit etc. can act normally,
then it will do high speed running.
7.1.4
High Speed Running
1
Give the floor normal run command so that to the elevator can run normally. Then set Group F02 of start &
stop parameters, start stopping parameters, adjust starting & stopping brake and motor running time
sequence to make sure that the elevator does not shake at start & stop.
•
For asyn. motor, adjust Group F02 to avoid obviously shaking at start & stop.
•
For syn. motor, set Group F06 additionally to avoid elevator brake at start.
•
If syn. motor has SINCOS encoder, it can achieve elevator smooth start using weigh less method (Group
F06). And F02.02 (Retention time of start zero-speed) is set at least as 0.5s.
2
If the elevator has slight shake at running, properly adjust Group F08.
7
Содержание MONT72 Series
Страница 1: ...V1 0 2018 09 MONT72 Series Elevator Controller User Manual MONT72 Series Elevator Controller ...
Страница 3: ...Version and Revision Records Version time 2018 9 Version V1 0 Chapter Content V1 0 issue ...
Страница 7: ......
Страница 9: ......
Страница 15: ......
Страница 43: ......
Страница 81: ......
Страница 99: ......