Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 66 -
MONT72 Series User Manual V1.0
6.2.16
F16: Function-boost Parameters
Ref. Code
Function Description
Setting Range [Default]
F16.00
Zero-speed running signal delay time
0.00 - 10.00 [0.30s]
Defines the delay time of MONT72 from zero-speed run status to zero-speed run signal output.
F16.01
Zero-speed signal delay time
0.00 - 10.00 [0.30s]
Defines the delay time of MONT72 from zero-speed status to zero-speed signal output.
F16.02
Current keep time after stop
0 - 9999 [0ms]
To eliminate the current noise of motor at stop, when the brake is finished, the cut-off run signal will reduce the
current to zero after the time of F16.02.
F16.03
Fan control mode
0 - 2 [0]
Defines the fan control mode. If there is overheat protection, the fan will run all the time.
0: Auto stop.
•
The fan runs all the time when MONT72 is in run status. After MONT72 stops for the time of F16.04, the fan
continues running if overheat protection is activated.
1: Immediately stop.
•
The fan runs all the time when MONT72 is in running status, but stops when MONT72 stops.
2: Run when power on.
•
The fan runs continuously after MONT72 is switched on.
F16.04
Fan control delay time
0.0 - 600.0 [300.0s]
F16.05
Brake unit action voltage
220V:
360 - 450 [380V]
380V:
630 - 750 [720V]
Note: The braking action enables only in run status.
F16.06
Contactor fault detect time
0.1 - 10.0 [2.0s]
F16.07
Multi-speed inspection
0 - 7 [0]
When the DI terminals are not enough, the MS1 - MS3 can achieve the inspection run.
•
DI terminal = inspection terminal INS (No. 7 function), only need set F16.07 as 0 to enter terminal inspection
run.
•
DI terminals ≠ inspection terminal INS (No. 7 function), the MS1 - MS3 can achieve inspection run.
•
Value of MS1 - MS3 = value of F16.07, enter MS inspection run at MS run speed (F05.00 - F05.07).
Note: When MS run speed (F05.00 - F05.07) exceeds 0.630m/s, run at 0.630m/s.
F16.08
Zero-speed threshold
0.001 - 0.010 [0.003m/s]
When the present run speed ≤ F16.08, the system run speed will be considered as 0. After zero-speed delay
signal, the zero-speed signal will output.
F16.09
Selection at motor overheat fault
0,1 [0]
0: When detect that the motor is overheated, alarms E0020 fault (motor overheat) after motor stops.
1: When detect that the motor is overheated, alarms E0020 fault (motor overheat) at once.
F16.11
Stationary auto-tuning and current limit of syn. motor
20 - 200 [120%]
F16.12
Delay time of run output signal
0.00 - 1.00s [0.00s]
F16.12 is used to delay the controller running signal (output = No. 2 function) so as to control MONT72 to open
the brake.
Содержание MONT72 Series
Страница 1: ...V1 0 2018 09 MONT72 Series Elevator Controller User Manual MONT72 Series Elevator Controller ...
Страница 3: ...Version and Revision Records Version time 2018 9 Version V1 0 Chapter Content V1 0 issue ...
Страница 7: ......
Страница 9: ......
Страница 15: ......
Страница 43: ......
Страница 81: ......
Страница 99: ......