Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 62 -
MONT72 Series User Manual V1.0
Ref. Code
Function Description
Setting Range [Default]
Note: Hundred digit = 0, normally open input selected; = 1, normally closed input selected.
0: Unused. Terminal function is unused. MONT72 ignores the signal input via this terminal.
•
The unused terminal is recommended to be set as 0 so as to avoid wrong connection or action.
1: Controller enabled (EN).
•
When enabled, MONT72 is enabled to run;
•
When unused, MONT72 is unused to run and will be in coasts to stop status.
•
When no terminal selects this function, it defaults that MONT72 is at enabled status.
2, 3: UP / DN.
•
Set control terminal to control up and down of elevator. The terminals are in below table.
(UP) terminal (No.2 function)
(DN) terminal (No. 3 function)
Elevator state
0
0
Stop
0
1
Down
1
0
Up
1
1
stop
4 - 6: Multi-speed terminal 1 - 3 (MS1 - MS3).
•
The operating curve of the 8-segment speed can be achieved by the logical combination of the
terminals, see the table below.
Multi-speed
terminal 3
(function No. 4)
Multi-speed
terminal 2
(function No. 5)
Multi-speed
terminal 1
(function No. 6)
Multi-speed setting
0
0
0
Multi-speed 0 (F05.00)
0
0
1
Multi-speed 1 (F05.01)
0
1
0
Multi-speed 2 (F05.02)
0
1
1
Multi-speed 3 (F05.03)
1
0
0
Multi-speed 4 (F05.04)
1
0
1
Multi-speed 5 (F05.05)
1
1
0
Multi-speed 6 (F05.06)
1
1
1
Multi-speed 7 (F05.07)
7: Inspection input (INS).
•
If enabled, elevator will do inspection running.
•
This signal, when used together with UP / DN (No. 2 or No. 3 function) command, can control the
elevator to go up or down during inspection.
8: Battery-driven input (BAT).
•
If enabled, elevator will enter battery-driven running status.
9: Contactor feedback input (CSM).
10: Brake feedback input (BSM).
11: Governor feedback input (OSG).
15: Motor overheat input (OH).
16: Fault reset input (RST).
•
When MONT72 alarms fault, reset it by this terminal.
•
The function of RST terminal is the same as the
key.
34: External fault (EXT).
•
The fault signal of external equipment can be input through this terminal, so MONT72 can monitor that
equipment and respond accordingly. MONT72 alarms E0024 fault (external fault) when receives the EXT
signal.
Содержание MONT72 Series
Страница 1: ...V1 0 2018 09 MONT72 Series Elevator Controller User Manual MONT72 Series Elevator Controller ...
Страница 3: ...Version and Revision Records Version time 2018 9 Version V1 0 Chapter Content V1 0 issue ...
Страница 7: ......
Страница 9: ......
Страница 15: ......
Страница 43: ......
Страница 81: ......
Страница 99: ......