Installation
8.
310
· 286 ·
Ref.1912
DDS
HARDWARE
How to install TWO resistors ER+TH-18/1100 in parallel to the BPM
module
F. H8/19
Connection of TWO external Ballast RESISTORS in parallel to the bus
protection module, BPM.
Always install both resistors vertically
Diagram for 2 resistors in parallel with an external thermostat
Connect the R-R terminals of the
r e s i s t o r t o t h e c o n n e c t i o n
terminals R1-R1 of the Ballast
connector of the BPM module
Connect according to the figure the terminal
l24 V DC to an external 24 V DC
power supply of the electrical cabinet and the
PLC INPUT to a PLC input.
IMPORTANT.
Remember to manage the chosen
PLC input in the PLC program to generate an
error when exceeding the limit temperature
(200°C) detected by the sensor and to open
the contact.
Connect the R-R terminals
of the resistor to the connec-
tion terminals R2-R2 of the
Ballast connector of the
BPM module.
Connector of the Ballast of the
BPM module
ER+TH-18/1100
ER+TH-18/1100
Содержание DDS APS-24
Страница 1: ...DRIVE DDS Hardware manual Ref 1912...
Страница 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 16: ...Ref 1912 DDS HARDWARE 16...
Страница 20: ...Ref 1912 DDS HARDWARE 20...
Страница 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Страница 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Страница 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Страница 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Страница 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Страница 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Страница 405: ......