TN diagram
Distribution diagram that has a point directly connected to ground and the
conductive parts of the installation are connected to this point through
ground protection conductors. This type of mains admits loads between one
or several phases and the neuter.
There are three kinds of TN diagrams depending on the relative position of
the neuter wire (N) and the protection wire (PE):
TN-S diagram
where the neuter wire (N) and the protection wire (PE)
are different in the entire diagram.
TN-C-S diagram
where the neuter and protection functions are
combined in a single wire (PEN) in part of the diagram.
TN-C diagram
where the neuter and protection functions are combined
in a single wire (PEN) in the entire diagram.
for properly installing the DDS system with a TN-C type
distribution diagram.
F. H6/4
TN-C type distribution diagram.
DDS
DDS
L1
L2
L3
DIFFERENTIAL
BREAKER
DDS
SECONDARY
WINDING OF THE
LINE TRANSFORMER
OF THE PLANT
DIFFERENTIAL
BREAKER
DIFFERENTIAL
BREAKER
MAINS
FILTER
PEN
MAINS
FILTER
MAINS
FILTER
TN-C diagram
INFORMATION.
The DDS system may be connected directly, through a
transformer or auto-transformer in mains with a TN type distribution diagram.
i
Содержание DDS APS-24
Страница 1: ...DRIVE DDS Hardware manual Ref 1912...
Страница 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 16: ...Ref 1912 DDS HARDWARE 16...
Страница 20: ...Ref 1912 DDS HARDWARE 20...
Страница 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Страница 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Страница 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Страница 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Страница 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Страница 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Страница 405: ......