Power line connection
6.
238
Ref.1912
DDS
HARDWARE
· 226 ·
shows the right and wrong installations so as
to avoid making mistakes during installation. This way, after the main switch
- S1
and in this order, go the protection fuses
- F
, the differential breaker
-
Q1
, the transformer to adapt mains to the supply voltage range ·only if
necessary·, the mains filter for electromagnetic disturbances and the power
contactor
- KM1
for turning the FAGOR DDS system ON/OFF.
MANDATORY.
Install the MAINS FILTER in the position indicated in figure
regarding the power contactor - KM1.
MANDATORY.
NEVER connect in parallel with the FAGOR DDS system other elements
such as moors, inductive components, etc. to avoid the risk of poor system
performance when stopping the machine.
ALWAYS connect the power supply of other equipment being installed and
run together with the FAGOR DDS system through a second contactor -
KM2 or through auxiliary contacts of the power (main) contactor - KM1.
Содержание DDS APS-24
Страница 1: ...DRIVE DDS Hardware manual Ref 1912...
Страница 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 16: ...Ref 1912 DDS HARDWARE 16...
Страница 20: ...Ref 1912 DDS HARDWARE 20...
Страница 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Страница 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Страница 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Страница 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Страница 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Страница 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Страница 405: ......