Power line connection
6.
238
Ref.1912
DDS
HARDWARE
· 228 ·
The fuse references given of the previous table are the ones that may be
installed to obtain the maximum power on each model. In those cases where
the power supply is oversized, the fuse value should be adjusted to the
actual requirements of the machine.
T. H6/3
Fuses to be installed in mains line depending on the power supply
installed.
MANUFACTURER
PS-25B4
XPS-25
RPS-20
PS-65A
XPS-65
RPS-45
RPS-75
RPS-80
BUSMANN
FWH45B
RF00-125A
-
XL50F-45A
XL50F-125A
-
RF-000-40A
RF-000-125A
-
40FE
100FE
160FE
170M2611
170M1318
170M1319
170M3009
170M3013
170M3014
GOULD
A00-66C5D8
A00-66C125D8
-
A00-66C5D1
A00-66C125D1
-
FERRAZ
6.9 gRB 00
D08L 040
6.9 gRB 00
D08L 125
6.9 gRB 00
D08L 160
6.6 gRB 000
D08/040
6.6 gRB 000
D08/100
6.6 gRB 000
D08/160
SIBA
20 189 20-50A
20 189 20-125A
20 189 20-160A
WICKMAN
45FEE
140FEE
-
SIEMENS
3NE8 003
3NE8 021
3NC8423-3
LITTELFUSE
-
L70S125
L70S150
T. H6/4
Fuses to be installed in mains line depending on the compact drive
installed.
ACD/SCD/CMC
SCD
MANUFACTURER
1.08
1.15
1.25
2.35/50
2.75
BUSSMANN
FC-6A
FC-12A
FC-20A
FWC-32A10F
-
XL50-10A
XL50-15A
RF-000-25 FWP-32A14F
-
6CT
12CT
-
-
-
FWH-6.30A6F
-
-
-
-
GOULD
ST-6
10x38
ST-12
10x38
ST-20
10x38
-
-
000-10
000-16
A60x20
-
-
000/80-10
000/80-16
-
-
-
FERRAZ
6.600CP URC
14.51/6
12.600CP URC
14.51/6
-
-
6.921CP URQ
27x60/63
6.621CP URC
14.51/6
12.621CP URC
14.51/6
-
-
-
6.6URE10/6
12.6URE10/6
-
-
-
A60Q6-2
A60Q12-2
A60Q20-2
A60Q30-2
-
A60X6-1
A60X12-1
-
-
-
SIBA
-
-
-
-
50-140-34.63
without striker
-
-
-
-
50 142 34.63
with striker
SIEMENS
-
-
3NE8 015
3NE8 003
-
WARNING.
Using other protection devices instead of fuses (magneto-
thermal switches, for example) does no guarantee proper protection of the
equipment.
MANDATORY.
When using an auto-transformer or an isolating transformer,
the fuses must be selected according to its characteristics depending on the
structure of the installation. Therefore, the fuses must be selected
specifically for each installation since it will be affected by a variable number
of characteristics internal and external to the machine.
Содержание DDS APS-24
Страница 1: ...DRIVE DDS Hardware manual Ref 1912...
Страница 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 16: ...Ref 1912 DDS HARDWARE 16...
Страница 20: ...Ref 1912 DDS HARDWARE 20...
Страница 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Страница 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Страница 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Страница 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Страница 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Страница 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Страница 405: ......