B614
39
732998 - Rev.A_DRAFT
Tr
ansla
tion of the original instruc
tions
ENGLISH
Basic function
Default
Sc
CLOSURE SPEED
01
minimum
speed
10
maximum
speed
See tab.
Speed de-
fault
bu
DEVICE REGISTRATION BUS 2easy
See the relative section.
no
M1
Dead-man MOTOR OPERATION mode
+
OPENS
(displaying
oP
) as long as the button
remains pressed.
-
CLOSES
(displaying
cL
) as long as the but-
ton remains pressed.
--
tL
SET-UP
Acquire the limit switch positions.
See the relative section.
no
St
LEAVING THE PROGRAMMING MODE
Y
save and exit from programming mode
no
exit from programming mode without
saving
Press
F
to confirm. After exiting, the display
indicates the status of the automation system:
00
=
Closed
01
=
Open
02
= Stationary then opens
03
= Stationary then closes
04
=
Pausing
05
=
Opening
06
=
Closing
07
= Failsafe underway
08
= Check of BUS 2easy device underway
09
= Pre-flashing and then opens
10
= Pre-flashing and then closes
11
= Opening in emergency
Y
10
Advanced programming
Advanced function
Default
PF
PRE-FLASHING
no
disabled
OC
preflashing 3 sec. before each movement
no
FO
DRIVING FORCE ON OPENING
01
minimum
power
50
maximum
power
50
FC
DRIVING FORCE ON CLOSURE
01
minimum
power
50
maximum
power
50
SP
STOP INPUT CONFIGURATION
It defines the function of the STOP input
00
(STOP)
Stop
02
(FSW-CL) Closure photoelectric cell
00
t
OPERATING TIME (time-out)
Set a higher value than the time the barrier needs
to open/close completely.
This can be regulated from 0 to 59 secs. in 1 sec
steps. Afterwards, the display changes in minutes
and tens of seconds (separated by a dot) and the
time is regulated in 10 sec. steps, up to a maximum
value of 9.5 minutes.
E.g.: if the display indicates
2.5
, the pause time is
2 min and 50 sec.
In the case of a plant with a Master/
Slave configuration an operating time
must be set on the Master central
control unit that takes account of the
movement of both the barriers.
5.0
o1
OUT OUTPUT 1 CONFIGURATION
00
Always
active
01
failsafe
02
telltale light (on during opening/pause/
open, flashing on closure, off when closed)
03
courtesy
light
05
barrier open or in pause mode
06
barrier
closed
07
barrier
moving
08
barrier in emergency mode
09
barrier
opening
10
barrier
closing
12
safety device active
13
light column (active in pause mode/open,
turns off on closure)
15
step by step activation through second radio
channel
19
battery
operation
20
Loop1
engaged
21
Loop2
engaged
00
9
Speed default
cF 01
cF 02
cF 03
So
10
06
02
Sc
08
04
02