![Ever SINLINE PRO 10000 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/ever/sinline-pro-10000/sinline-pro-10000_instruction-manual_2442536008.webp)
Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
8
USER INTERFACE
The user interface consists of a four-button keypad located on the upper cover of the
power supply unit, an LCD, and three LEDs. They allow the user to monitor the unit's
operating parameters, and also modify some of them. The method of using the
interface and the meanings of individual parameters have been described hereunder.
Figure 3: View of the user interface
Table 1 Meanings of signalling diodes
Graphical symbol
Designation
Description
LED 1
LED indicating the unit's operation mode: NORMAL/BACKUP
AVR
LED 2
LED signalling activation of the AVR system
LED 3
LED signalling activation of the EMERGENCY mode
Table 2 Optical (diode) signalling
LED 1
LED 2 LED 3 Operation mode
UNKNOWN
F
NORMAL
BACKUP
STANDBY
READINESS
*
EMERGENCY
INIT
STOP
F - the status may be configuration-dependent (none or red);
* - flashes
The unit is also equipped with an audible signalling system for its respective states
(cf. table).
Table 3 Audible signalling
Action
Audible signalling
NORMAL mode
None
BACKUP mode
intermittent signal, rapidity dependent on the charge level of batteries
(the more rapid the signal, the lower the battery charge level)
Forced switch to the
STANDBY mode
intermittent signal - two successive short signals followed by a pause
EMERGENCY mode
Event dependent
Overload
continuous signal
Short circuit
rapid intermittent 50% / 50% signal
Overheat
slow intermittent 50% / 50% signal
EPO activation
intermittent sound/silence (1s / 5s) signal
All successive screens shown on the LCD are organised in a tree structure, as
presented in the following figure.
Содержание SINLINE PRO 10000