Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
28
Once it has been correctly connected, start up the power supply unit by performing
the following activities in the order mentioned:
1)
Check whether fuses F3 and F4 are OFF; if not, set them OFF.
2)
Open the mounts of fusible cut-outs F1 and F2.
3)
Insert an appropriate fuse-element in mount F1 (do not close the mount).
4)
Insert an appropriate fuse-element in mount F5, and then close it in order to
close the circuit.
5)
mount of the battery module's fusible cut-out and close the circuit by closing the
mount.
6)
Close mount F1.
7)
Wait at least 10 sec.
8)
Close mount F2 – the batteries are connected.
9)
Switch fuses F3 and F4 ON.
10) Set the configuration of the power supply unit (when starting up for the first time,
if modifications are required).
11) Switch on the power supply unit by means of the user interface (CONTROL 1/3;
UPS).
Points 4 and 5 should be performed only if an additional battery module is connected.
Once these actions are performed, the power supply unit will commence normal
operation.
NOTE! The batteries of the power supply unit attain full power after
approx. one month of operation in NORMAL mode.
SWITCHING OFF AND DISCONNECTING THE POWER SUPPLY UNIT
In order to completely disconnect the power supply unit, perform the following
activities in the order mentioned:
1)
Switch the power supply unit off by means of the user interface (CONTROL
1/3;UPS) – logical switch-off;
2)
Disconnect the safeguards of the main line and the BYPASS in the
room/building switching station in order to safely uninstall the power supply unit.
3)
Set safeguards F3 and F4 in the power supply unit OFF.
4)
Disconnect safeguards F1, F2 and F5 - to this end, open them and remove the
fuse-elements.
5)
If battery modules are connected to the power supply unit, repeat point 4 for
safeguards F1 and F2 w in these modules.
6)
Remove the protective plugs of connecting elements on the power supply unit
and on modules (if any).
7)
Disconnect the connecting cables from the switching stations, power supply unit
and modules (also between modules). It is strictly forbidden to leave any loose
wires.
8)
Reinstall the protective plugs.
9)
Close the mounts of fusible cut-outs F1, F2 and F5 in the power supply unit and
of F1 and F2 in the modules, if the fuse-elements have been removed. The
fuse-elements should not be stored in the power supply unit if it is not installed.