![Ever SINLINE PRO 10000 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/ever/sinline-pro-10000/sinline-pro-10000_instruction-manual_2442536035.webp)
Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
35
Installing a management card
1)
Switch on the power supply unit by means of the user interface (CONTROL 1/3;
UPS).
2)
Set safeguards F3 and F4 OFF.
3)
Switch off safeguards F1, F2 and F5 by opening the fusible cut-out mounts. The
safeguards do not have to be switched off in any special order.
4)
Wait for approx. 30 sec. in order to discharge the internal capacities of the unit.
5)
Unscrew the metal grille from the card socket.
6)
Connect the card cable (the cable is located in the card slot.
7)
Insert the card into the slot.
8)
Screw the card grille to the rear panel.
9)
Activate safeguard F1 by closing the mount.
10) Wait at least 10 sec.
11) Activate safeguard F2 by closing the mount.
12) Activate safeguard F5 by closing the mount.
13) Set safeguards F3 and F4 ON.
14) Switch on the power supply unit by means of the user interface (CONTROL 1/3;
UPS).
Figure 5: Installation of the card
Содержание SINLINE PRO 10000