Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
29
OPERATING MODES OF THE POWER SUPPLY UNIT
Figure 5: Graph presenting the operation modes of the power supply unit
UNKNOWN mode
An intermediate state that occurs when the power supply unit is started up
following energisation.
INIT (INITIALISATION) mode
An intermediate state that occurs following initiation of the hardware platform
by means of start-up values or during a return from EMERGENCY mode.
NORMAL mode (MAINS OPERATION)
In for the power supply unit to be in NORMAL mode, it must by logically switch
on (from the user interface). In addition, the input primary power line must satisfy the
mains correctness criteria (correct value of voltage and frequency). The unit then
supplies power to the outputs from the abovementioned line, with the AVR system
making the necessary corrections. In this mode, the batteries are topped up.