Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
34
Switch in the UPS position – normal operation of the power supply unit.
Switch in the BYPASS position – the BYPASS line is switched to the input terminals.
Switching may be performed at any time.
COOPERATION OF THE POWER SUPPLY UNIT WITH A PC
RS232 AND USB COMMUNICATION
The user can modify the parameters of the power supply unit not only from the
user interface (panel), but also by means of the dedicated PowerSoft software.
Please note, however, that this software does not enable changing all of the
configuration parameters available from the device's panel.
SINLINE PRO 10000 series power supply units have been provided with advanced
management options. The user has at his disposal two RS232 and USB
communication links and the PowerSoft Personal programme, which is delivered with
unit. To maintain the desired cooperation, it is necessary to connect the unit to a free
computer port by means of the attached cable. Once the cable is connected, you
should turn on the power supply unit, switch on the computer and install the software
proceeding in accordance with the attached instruction or the installation wizard
prompts (for Microsoft Windows).
NOTE! Only one link may be used at any one time.
The RS232 and USB ports are separated galvanically from the remaining blocks of
the unit.
EVER SNMP/HTTP NETWORK MANAGEMENT CARD
The EVER management card is optional and may be installed by the user. It
serves to integrate the power supply unit with an Ethernet-based computer network.
The network card is located in a special slot on the rear wall of the unit. The card
allows the user to manage the unit from any computer in the network. This solution is
most frequently used in the event of centralised power supply, or if it is necessary to
manage the power supply system remotely.
The network card has the following services implemented:
•
SNMP agent – the power supply system may be managed by means of "SNMP
Manager" software;
•
HTTP server – possibility of viewing and modifying power supply unit
parameters using an internet browser;
•
Telnet server – management by means through a Telnet network terminal;
More information about the network card may be found in its instruction manual.
NOTE! If the SNMP card is connected, communication through the
RS232 and USB links is disable, while the PowerSoft Personal
programme is unavailable.