Instruction manual for SINLINE PRO 10000 series power supply units
2010/08/24
www.ever.eu
25
10. Replace the fuse-elements in their respective mounts.
11. Close the fusible cut-out mounts of all connected battery modules in turn.
12. Close the F1 mount in the power supply unit.
13. Wait at least 10 sec.
14. Close the F2 mount in the power supply unit – the batteries are connected.
15. Switch fuses F3 and F4 ON.
16. Set the appropriate battery-related parameters of the power supply unit
(CONFIGURATION 4/4).
17. Switch off the power supply unit by means of the user interface (CONTROL 1/3;
UPS).
Display data that directly concerns the number of connected batteries will be
automatically updated once the batteries are topped up Until this happens, the
information given may be inaccurate.
Disconnecting modules
1.
Switch off the power supply unit by means of the user interface (CONTROL 1/3;
UPS).
2.
Set fuses F3 and F4 in the power supply unit OFF.
3.
Disconnect the safeguards of the main line and the BYPASS in the
room/building switching station.
4.
Disconnect safeguards F1, F2 and F5 in the power supply unit and F1 and F2
all battery modules – to do this, open the fusible cut-out mounts and remove the
fuse-elements.
5.
Remove the plugs of connecting elements.
6.
Disconnect the modules. The connecting cables must be fully disconnected.
7.
Secure the connecting elements by screwing in the protective plug.
8.
Activate the safeguards in the switching station of the room/building.
9.
Replace the fuse-elements in their respective mounts.
10. Close the fusible cut-out mounts of all connected battery modules in turn (if any
are still connected).
11. Close the F1 mount in the power supply unit.
12. Wait at least 10 sec.
13. Close the F2 mount in the power supply unit – the batteries are connected.
14. Switch fuses F3 and F4 ON.
15. Set the appropriate battery-related parameters of the power supply unit
(CONFIGURATION 4/4).
NOTE! It is forbidden to leave loose cable ends. They could be
under a voltage that is dangerous to health and/or life.