Application Macros
15-14
605 Series Frequency Inverter
Macro 6: Closed-Loop Speed Feedback
Encoder speed feedback.
PID speed regulation loop.
Additional Operator Menu display parameters.
Terminal
Terminal
Terminal
Terminal
Name
Name
Name
Name
Purpose
Purpose
Purpose
Purpose
Comment
Comment
Comment
Comment
2
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
4
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
5
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand, 0V =
0%, 10V = 100%
7
DIGITAL INPUT 1
Run
24V = Run
8
DIGITAL INPUT 2
Trip Reset
0V to 24V transition to reset trips.
9
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
10
DIGITAL INPUT 4
External Trip
0V = Trip (connect to terminal
18)
11
DIGITAL INPUT 5
PID Enable
0V = PID Disabled, 24V = PID
Enabled
13
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
14
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 6
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
PID OUT SCALING
STARTUP SCREEN
PID P GAIN
PID I TIME CONST
PID D TIME CONST
PID FILTER TC
PID SETPOINT
PID FEEDBACK
PID ERROR
ENTER PASSWORD
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...