Certification for the Inverter
12-5
605 Series Frequency Inverter
3 Metal Work Earth Busbar
The back panel is used as this earth busbar, and should provide earthing points for all parts of the
cubicle including panels and doors. This busbar is also used for power screened cables which
terminate near to (10cm) or directly into a VSD - such as motor cables, braking choppers and
their resistors, or between VSDs - refer to the appropriate product manual to identify these. Use
U-clips to clamp the screened cables to the back panel to ensure optimim HF connection.
4 Signal/Control Screen Earth Busbar (insulated from the mounting panel)
Used for signal/control screened cables which
do not
go directly to the VSD. Place this busbar
as close as possible to the point of cable entry. `U’ clamp the screened cables to the busbars to
ensure an optimum HF connection.
Sensitive Equipment
The proximity of the source and victim circuit has a large effect on radiated coupling. The
electromagnetic fields produced by VSDs falls off rapidly with distance from the cabling/cubicle.
Remember that the radiated fields from EMC compliant drive systems are measured at least 10m
from the equipment, over the band 30-1000MHz. Any equipment placed closer than this will see
larger magnitude fields, especially when very close to the Inverter.
Do not place magnetic/electric field sensitive equipment within 0.25 metres of the following
parts of the VSD system:
•
Variable Speed Drive (VSD)
•
EMC motor output filters
•
Input or output chokes/transformers
•
The cable between VSD and motor (even when screened/armoured)
•
Connections to external braking chopper and resistor (even when screened/armoured)
•
AC/DC brushed motors (due to commutation)
•
DC link connections (even when screened/armoured)
•
Relays and contactors (even when suppressed)
From experience, the following equipment is particularly sensitive and requires careful
installation.
•
Any transducers which produce low level analog outputs (<1V) , e.g. load cells, strain
gauges, thermocouples, piezoelectric transducers, anemometers, LVDTs
•
Wide band width control inputs (>100Hz)
•
AM radios (long and medium wave only)
•
Video cameras and closed circuit TV
•
Office personal computers
•
Capacitive devices such as proximity sensors and level transducers
•
Mains borne communication systems
•
Equipment not suitable for operation in the intended EMC environment, i.e. with insufficient
immunity to new EMC standards
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...