![Eurotherm 605 Series Скачать руководство пользователя страница 190](http://html.mh-extra.com/html/eurotherm/605-series/605-series_product-manual-installation-and-instructions_2440552190.webp)
12-4
Certification for the Inverter
605 Series Frequency Inverter
Single VSD - Multiple Motors
Note:
Refer to Chapter 13: “Application Notes” - Using Multiple Motors on a Single Inverter.
IMPORTANT:
If connecting multiple motors to a single VSD, use a star junction point for motor cable
connections. Use a metal box with entry and exit cable glands to maintain shield integrity.
Refer to Chapter 13: “Using Multiple Motors on a Single Inverter”.
Star Point Earthing
A star-point earthing policy separates `noisy’ and `clean’ earths. Four separate earth busbars
(three are insulated from the mounting panel) connect to a single earth point (star point) near the
incoming safety earth from the main supply. Flexible, large cross-section cable is used to ensure
a low HF impedance. Busbars are arranged so that connection to the single earth point is as short
as possible.
1 Clean Earth Busbar (insulated from the mounting panel)
Used as a reference point for all signal and control cabling. This may be further subdivided into
an analogue and a digital reference busbar, each separately connected to the star earthing point.
The digital reference is also used for any 24V control.
2 Dirty Earth Busbar (insulated from the mounting panel)
Used for all power earths, i.e. protective earth connection. It is also used as a reference for any
110 or 220V control used, and for the control transformer screen.
Doors
Metal
Work
110V
Control
24V Control
unscreened signals
STAR POINT
Incoming Safety Earth (PE)
Analogue Clean Earth
Dirty Earth
Digital Clean Earth
Signal/Control Screen
all screened signals not
Back Panel
U-clip used to terminate screen
connection to the back panel
PE = Protective Earth
0A = 0 Volts Analogue
0D = 0 Volts Digital
f = External Filter
VSD = Variable Speed Drive
PLC = Programmable Logic Controller
going directly to a VSD
Metal Work Earth
Back
Panel
PLC
PE
PE
PE
0D
0D
0D
0D
0A
0A
0A
to motor
to motor
to motor
screened
screened
PE
VSD
VSD
VSD
f
f
f
f
PE
PE
PE
Figure 12-2 Star Point Earthing
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...