Sequencing Logic
9-1
605 Series Frequency Inverter
9
S
EQUENCING
L
OGIC
S
TATES
Principle State Machine
The Inverter’s reaction to commands is defined by a state machine. This determines which
commands provide the demanded action, and in which sequence.
Main Sequencing States
The main sequencing state of the unit is indicated by an enumerated value given by the parameter
MAIN SEQ STATE under SEQUENCING LOGIC menu at level 4.
Enumerated
Enumerated
Enumerated
Enumerated
Value
Value
Value
Value
Main Seq State
Main Seq State
Main Seq State
Main Seq State
Standard Name
Standard Name
Standard Name
Standard Name
Description
Description
Description
Description
0
NOT READY
Not Ready To Switch On
Power up initialisation, or
configuration mode. No
command will be accepted
1
START DISABLED
Switch On Disabled
The Inverter will not accept a
switch on command
2
START ENABLED
Ready To Switch On
The Inverter will accept a switch
on command
3
SWITCHED ON
Switched On
The Inverter’s stack is enabled
4
ENABLED
Enabled
The Inverter is enabled and
operational
5
F-STOP ACTIVE
Fast-Stop Active
Fast stop is active
6
TRIP ACTIVE
Trip Active
The Inverter is processing a trip
event
7
TRIPPED
Tripped
The Inverter is tripped awaiting
trip reset
Table 9-1 Enumerated Values for the SEQUENCING LOGIC Function Block
State Outputs of the SEQUENCING LOGIC Function Block
The following table shows the states of individual parameters for the SEQUENCING LOGIC
function block required to produce the condition of the MAIN SEQ STATE parameter.
NOT
NOT
NOT
NOT
READY
READY
READY
READY
START
START
START
START
DISABLED
DISABLED
DISABLED
DISABLED
START
START
START
START
ENABLED
ENABLED
ENABLED
ENABLED
SWITCHED
SWITCHED
SWITCHED
SWITCHED
ON
ON
ON
ON
ENABLED
ENABLED
ENABLED
ENABLED F-STOP
F-STOP
F-STOP
F-STOP
ACTIVE
ACTIVE
ACTIVE
ACTIVE
TRIP
TRIP
TRIP
TRIP
ACTIVE
ACTIVE
ACTIVE
ACTIVE
TRIPPED
TRIPPED
TRIPPED
TRIPPED
Tripped
Tripped
Tripped
Tripped
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
TRUE
Running
Running
Running
Running
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
Jogging
Jogging
Jogging
Jogging
FALSE
FALSE
FALSE
FALSE
Note 1
FALSE
FALSE
FALSE
Stopping
Stopping
Stopping
Stopping
FALSE
FALSE
FALSE
FALSE
Note 2
TRUE
FALSE
FALSE
Output
Output
Output
Output
Contactor
Contactor
Contactor
Contactor
FALSE Depends
on
previous
state
Depends
on
previous
state
TRUE
TRUE
TRUE
TRUE
FALSE
Switch On
Switch On
Switch On
Switch On
Enable
Enable
Enable
Enable
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
Switched
Switched
Switched
Switched
On
On
On
On
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
FALSE
Ready
Ready
Ready
Ready
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
FALSE
Healthy
Healthy
Healthy
Healthy
O/P
O/P
O/P
O/P
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
FALSE
Note 3
Table 9-2 Parameter States for the MAIN SEQ STATE Parameter
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...